(1) Analog input terminals (13, 12, C1, and 11)
1. These terminals receive low level analog signals that
may be affected by external noise. The cables must
be as short as possible (20 meters or less), must be
shielded, and the shields must be grounded. If the
cables are affected by external induction noise, the
shielding effect may be improved by connecting the
shield to terminal [11].
2. If contacts must be connected to these circuits, twin
(bifurcated) contacts for handling low level signals
must be used. A contact must not be connected to
terminal [11].
3. If an external analog signal output device is con-
nected to these terminals, it may malfunction as a
result of drive noise. To prevent malfunction, connect
a ferrite core or capacitor to the external analog
signal output device.
Data subject to change without notice 7/07. © 2007 GE Drives
Transistor output 1
Transistor output 2
Transistor output 3
Transistor output 4
Transistor output common
Alarm outputs for any fault.
Multi-purpose signal
RTU communication
Communication cable
shield connection terminal
A running signal, frequency equivalence signal, overload early
warning output signal, and other signals from the drive are output
(as transistor output) to arbitrary ports. For details, see "Setting the
Terminal Functions E20 to E23" in Section 5.2 Function Explanation.
* <Specifications of transistor output circuit>
Item
Operating voltage
ON
OFF
Maximum load current
ON
Leakage current
OFF
Common terminal for transistor output signals. This terminal is
insulated from terminals (CM) and [11].
If the drive is stopped by an alarm (protective function), the alarm
signal is output from the relay contact output terminal (1SPDT).
Contact rating: 250 VAC, 0.3A,cosØ = 0.3, 48 VDC, 0.5A for CE
Marking
An excitation mode (excitation at alarm occurrence or at normal
operation) can be selected.
These signals can be output similar to the Y1 to Y4 signals above.
The contact rating is the same as that of the alarm output above.
Input / output signal terminals for RTU communication input / output
Up to 31 inverters can be connected using the daisy chain method.
Terminal for connecting the cable shield. The terminal is electrically
floating.-
Shielded wires
VR
1k to
5K ohms
Fig. 2-3-9
Fig. 2-3-10 Example of Noise Prevention
2-13
min. typ.
max.
1V
2V
24V
27V
50 mA
0.1 mA
Drive
13
12
11