(2) Control circuit terminals
30A Y5A CMY Y3
30C 30B Y5C
Y4
2.3.5 AF-300 P11 Drive Cable Size, Tightening Torque and Circuit Protection Rating
Input Fuse
HP
L1/R, L2/S, L3/T
L1/R, L2/S, L3/T
(Nominal)
(Maximum) (*1)
230 VAC Input
0.25
3
3
0.5
5
6
1
10
15
2
15
20
3
20
30
5
35
50
7.5
60
80
10
70
125
15
100
150
20
125
200
25
150
225
30
175
250
40
200
-
50
225
-
60
300
-
75
350
-
100
300
-
125
400
-
150
450
-
460 VAC Input
0.5
3
3
1
5
6
2
10
10
3
15
15
5
20
25
7.5
30
45
10
40
60
15
50
90
20
70
110
25
80
125
30
100
125
40
100
-
50
125
-
60
150
-
75
175
-
100
150
-
125
200
-
150
225
-
200
300
-
250
400
-
300
450
-
350
500
-
400
600
-
450
700
-
500
700
-
600
1000
-
700
1000
-
800
1200
-
(*1)Class J Fuse or Circuit Breaker reted 600V with the maximum current rating as shown in the above table shall be connected to the drive for 30HP and less.
(*2)Based on GE Fuji standard DB unit and DB resistor designs. Other rating require careful review.
(*3) Consult factory
Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Wire size from NEC tables 310-16. Copper wire rated 60 Deg. C for 100amps or less, 75 Deg. C for over 100 amps in 30 Deg. C ambient and 1.25 times Drive rated amps.
These are minimum wire sizes : consult and conform to local and national codes.
Y1
C1 FMA FMP PLC
Y2
11
12
13
Incoming Device
Tightening Torque lb-Inch (Nm)
L1/R, L2/S,
Input Circuit
Auxiliary
L3/T, U, V,
Breaker (*1)
Input
W, P1, P(+)
R0, T0
3
15
10.6 (1.2)
3
15
3
20
3
30
20.8 (2.36)
3
40
3
60
3
100
31.0 (3.5)
3
125
3
175
51.3 (5.8)
3
225
3
250
3
300
5
200
119(13.5)
5
225
5
300
239(27)
119(13.5)
5
350
5
300
5
400
425(48)
5
450
3
15
10.6 (1.2)
3
15
3
15
20.8 (2.36)
3
20
3
35
3
50
31.0 (3.5)
3
70
3
90
51.3 (5.8)
3
110
3
150
3
175
10
100
119(13.5)
10
125
10
150
10
175
10
150
10
200
239(27)
119(13.5)
10
225
10
300
10
400
425(48)
10
450
10
500
10
600
10
700
10
700
10
1000
10
1000
10
1200
X1
X2
X3
V2
CM
CM FWD REV P24 P24 DX- DX+
DB circuit
Control L1/R, L2/S,
E(G)
R0, T0
(*2) P(+),
N(-), DB
10.6
-
6.2 (0.7)
(1.2)
-
-
20.8
10.6 (1.2)
(2.36)
31.0
(3.5)
Qty2 - 1
119
Qty2 - 2/0
(13.5)
Qty2 - 3/0
Qty 2 - 2/0
239(27)
Qty2 - 4/0
Qty2 - 250
10.6
-
6.2 (0.7)
(1.2)
-
20.8
10.6 (1.2)
(2.36)
31.0
(3.5)
51.3
(5.8)
239(27)
119
Qty2 - 1/0
(13.5)
Qty2 - 1/0
239
Qty2 - 3/0
(27)
Qty2 - 4/0
Qty2 - 250
(*3)
Qty2 - 350
Qty2 - 350
Qty2 - 500
Qty3 - 300
Qty3 - 400
Qty3 - 500
2-16
Data subject to change without notice 7/07. © 2007 GE Drives
X4
X5
X6
X7
Cable size AWG
DB circuit
DC Reactor
U, V, W
(*2) P(+),
L3/T
P1, P(+)
N(-), DB
16
16
14
14
10
8
6
4
3
2
1
4/0
1/0
2/0
3/0
4/0
10
4/0
Qty2 - 1
Qty2 - 1/0
Qty2 - 2/0
8
Qty2 - 3/0
Qty2 - 4/0
6
Qty2 - 4/0
Qty2 - 250
4
Qty2 - 300
Qty2 - 350
16
16
14
14
12
10
8
6
4
2
3
3
1
2
2
2/0
2
1
3/0
1/0
2/0
2/0
3/0
4/0
3/0
4/0
Qty2 - 1
10
Qty2 - 1/0
Qty2 - 1/0
8
Qty2 - 2/0
Qty2 - 3/0
Qty2 - 3/0
Qty2 - 4/0
6
Qty2 - 250
Qty2 - 300
4
Qty2 - 300
Qty2 - 350
Qty2 - 350
Qty2 - 500
(*3)
Qty2 - 400
Qty2 - 500
Qty3 - 300
Qty3 - 300
Qty3 - 350
Qty3 - 500
Qty3 - 500
Qty3 - 600
Qty3 - 600
Qty3 - 600
X8
X9
SD
R0,
Control
T0
-
22
-
-
14