EK280

6.3 Status output (signal output)

Each of the outputs 1 to 4 (terminals DA1 to DA4) can be programmed as a status output (signal output).

6.3.1 Parameterizing by keyboard

i
The use of enSuite parameterizing software is strongly recommended for parameterizing a
status output (see below).
Parameterization with the keyboard on the EK280 is described below.
Setting up the output mode:
Move the cursor to the tab "Serv." and subsequently via the following path to the mode for the
corresponding output "Md.O1" to "Md.O4":
Serv.
Outputs
Serv.
Outputs
Serv.
Outputs
Serv.
Outputs
i
The status outputs of the EK280 can be operated with active or inactive logic. The output mode
must be programmed accordingly for this purpose (see below).
Press the ENTER  button. The actual parameterized value flashes.
Press one of the arrow buttons  or  until the
"status+"
(Logic active: message is active, when the output is switched on.) or
inactive: message is active, when the output is switched off) flashes.
Press the ENTER button to confirm the value setting. Input can be canceled using the ESC key.
Setting up the status display for the output:
When in the corresponding menu press the  button repeatedly until "SpO1", "SpO2", "SpO3", or
"SpO4" is displayed.
Press the ENTER  button. The actual parameterized value flashes.
Move the cursor to the digits using the  or  arrow keys and update them using the  or  arrow
keys to a value specified in the table.
Sc.O...
0.mm_0s:1.1 *
0.mm_02:2.1 *
0.mm_01:2.1 *
1.mm_0s:1.1 *
1.mm_02:2.1 *
1.mm_01:2.1 *
* mm = report-number (1...16), s = status number (1...9 for St.1 ... St.9)

6.3.2 Parameterizing with enSuite

The setting of the required report (or range) in particular can be conveniently set with enSuite.
The paths which are described below can be found in enSuite under
"Parameterize
Setting up the output mode:
First of all, the mode must be set to the required value:
"status+"
(Logic active: message is active, when the output is switched on.) or
"status-"
(Logic inactive: Report is active, when the output is switched off.)
Output 1
Md.O1
Output 2
Md.O2
Output 3
Md.O3
Output 4
Md.O4
Description
A report in a Status St.1 to St.9
A report in system status StSy
A report in overall status Stat
Message group in system status StSy
VmD Actual volume disturbance quantity
Message group in overall status Stat
online" > "Parameters" > "Outputs"
Application Manual
37
"status-"
(Logic