Handling Errors and Alarms
3-8-3

Errors in the CPU Unit

ERH and RUN Indicators: Lit
I/O bus error
CPU Unit monitoring error (see
note)
CPU Unit WDT error
ERH Indicator: Lit, RUN Indicator: Not Lit
Duplicate Unit Number
Special I/O Unit Setting Error
126
The ERH indicator will light if an error occurs in the CPU Unit or I/O bus and I/
O refreshing with the Special I/O Units is not performed correctly, preventing
the Analog Input Unit from operating.
The ERH and RUN indicators will be lit if an error occurs in the I/O bus caus-
ing a WDT (watchdog timer) error in the CPU Unit, resulting in incorrect I/O
refresh with the Analog Input Unit.
Turn ON the power supply again or restart the system.
For further details, refer to CJ-series CJ1G-CPU@@, CJ1G/H-CPU@@H Pro-
grammable Controllers Operation Manual (W393).
Error
Error has occurred during data
exchange with the CPU Unit.
No response from CPU Unit dur-
ing fixed period.
Error has been generated in
CPU Unit.
The unit number for the Analog Input Unit has not been set correctly.
Error
The same unit number has been
assigned to more than one Unit
or the unit number was set to a
value other than 00 to 95.
The Special I/O Units registered
in the I/O table are different from
the ones actually mounted.
RUN
ERC
ERH
Error contents
RUN
ERC
ERH
Error contents
Section 3-8
: Lit
: Not lit
Input status
Conversion data becomes 0000.
Maintains the condition existing
before the error.
Changes to undefined state.
: Lit
: Not lit
Input status
Conversion does not start and
data becomes 0000.