Omron CJ1W-AD041-V1 Manual page 18

Cj-series
Hide thumbs Also See for CJ1W-AD041-V1:
Table of Contents

Advertisement

Analog Input Functions and Operating Procedures
Set Values and Stored
Values
3-6
Analog Input Functions and Operating Procedures
3-6-1
Input Settings and Conversion Values
Input Numbers
106
Refer to 3-7-1 Adjustment Mode Operational Flow for further details.
Item
Input to be adjusted
Offset (Offset Bit)
Gain (Gain Bit)
Down (Down Bit)
Up (Up Bit)
Set (Set Bit)
Clr (Clear Bit)
Conversion value for
adjustment
Disconnection detection
Alarm Flags
Note For the CIO word addresses, n = CIO 2000 + (unit number × 10).
The input disconnection detection function can be used when the input signal
range is set for 1 to 5 V (4 to 20 mA).
Input signal range
1 to 5 V
4 to 20 mA
The Analog Input Unit converts analog inputs specified by input numbers 1 to
8 (1 to 4 for CJ1W-AD041-V1) only. To specify the analog inputs to be used,
turn ON from a Programming Device the D(m) bits in the DM Area shown in
the following diagram.
Bit
15 14
D(m)
Note There are only four inputs for the CJ1W-AD041-V1.
The analog input sampling interval can be shortened by setting any unused
input numbers to 0.
Sampling interval = (1 ms) x (Number of inputs used) (See note.)
Sets input to be adjusted.
Leftmost digit: 2 (fixed)
Rightmost digit: 1 to 8 (1 to 4 for CJ1W-AD041-V1)
When ON, adjusts offset error.
When ON, adjusts gain error.
Decrements the adjustment value while ON.
Increments the adjustment value while ON.
Sets adjusted value and writes to EEPROM.
Clears adjusted value. (Returns to default status)
The conversion value for adjustment is stored as 16 bits
of binary data.
0:
No disconnection
1:
Disconnection
Bit 12: Input value is outside adjustment limits
(in adjustment mode)
Bit 13: Input number setting error
(in adjustment mode)
Bit 14: EEPROM write error (in adjustment mode)
Bit 15: Operating in adjustment mode
(always 1 in adjustment mode)
Voltage/current
0.3 V max.
1.2 mA max.
13
12
11
10
09 08
Section 3-6
Contents
07
06
05
04
03 02
0: Not used
1: Used
01
00