When the outdoor unit is connected to a benefit kWh rate power
supply, the voltage free contact of the receiver controlling the benefit
kWh rate signal of the electricity company must be connected to
clamps 17 and 18 of X2M (as illustrated in the figure above).
When parameter [D-01]=1 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
When parameter [D-01]=2 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
Type 1
This type of benefit kWh rate power supply is not interrupted.
Type 2
This type of benefit kWh rate power supply is interrupted after elapse
of time.
Type 3
This type of benefit kWh rate power supply is interrupted
immediately.
When connecting the equipment to a benefit kWh rate
power supply, change field setting [D-01]. In case the
benefit kWh rate power supply is of the type that power
supply is not interrupted (like illustrated above as type 1)
change both field settings [D-01] and [D-00]. Refer to
"[D] Benefit kWh rate power supply/Local shift value
weather dependent" on page 30 of chapter "Field settings".
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, the unit will be forced to
off.
When the benefit kWh rate signal is sent, the centralised
control indicator e will flash to indicate that the benefit
kWh rate is active.
Relocation of the digital controller
The digital controller is from factory located on the indoor unit. (See
"Main components" on page 10 for actual position). If required, the
digital controller can be repositioned.
Be aware that only 1 digital controller can be connected to the indoor
unit.
Wiring specifications
Wire specification
Type
Section
Maximum length
NOTE
The wiring for connection is not included.
(1) When the signal is released again, the voltage free contact will close and the unit
will restart operation. It is therefore important to leave the auto restart function
enabled. Refer to "[3] Auto restart" on page 24.
(2) When the signal is released again, the voltage free contact will open and the unit
will restart operation. It is therefore important to leave the auto restart function
enabled. Refer to "[3] Auto restart" on page 24.
RKHBH/X008BA
Indoor unit for air to water heat pump system
4PW54224-1A
(1)
.
(2)
.
Value
2 wire
2
0.75-1.25 mm
500 m
Mounting
NOTE
The digital controller has to be mounted indoors.
1
Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the digital controller, and
remove the front part of the digital
controller.
2
Fasten the digital controller on a flat
surface.
NOTE
Be careful not to distort the shape of the lower part of
the digital controller by over tightening the mounting
screws.
3
Wire the unit.
6
1
1
2
P2
P1
P2
3
4
1
Unit
2
Rear part of the digital controller
3
Front part of the digital controller
4
Wired from the rear
5
Wired from the top
6
Notch the part for the wiring to pass through with nippers, etc.
Connect the terminals on top of the front part of the digital
controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTE
When wiring, run the wiring away from the
power supply wiring in order to avoid
receiving electric noise (external noise).
Peel the shield for the part
that has to pass through the
inside of the digital controller
case ( l ).
4
Reattach the upper part of the digital controller.
CAUTION
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the
bottom.
1
P1
5
1