About connecting the electrical wiring......39 6.2.2 Additional installation site requirements of the 7.9.2 About electrical compliance ......... 39 outdoor unit in cold climates ........23 Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Checklist for yearly maintenance of the indoor unit....76 12 Troubleshooting DANGER 12.1 Overview: Troubleshooting............77 Indicates a situation that results in death or serious injury. 12.2 Precautions when troubleshooting ..........77 RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
(example: thinner or gasoline), carbon fibre, comply with applicable legislation (on top of the ignitable dust. instructions described in the ROTEX documentation). ▪ In places where corrosive gas (example: sulphurous acid gas) is CAUTION produced. Corrosion of copper pipes or soldered parts may cause Wear adequate personal protective equipment (protective the refrigerant to leak.
When the refrigerant charging procedure is done or when pausing, close valve refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ NEVER squeeze bundled cables and make sure they ▪ Format: Digital files on the ROTEX homepage do not come in contact with the piping and sharp ▪ Addendum book for optional equipment: edges.
Multilingual fluorinated greenhouse gases label Unit mounting plate Indoor unit 3.3.1 To unpack the indoor unit 3.2.2 To remove the accessories from the outdoor unit 1 Lift the outdoor unit. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
2 Tilt the bottom side of the front panel upwards and remove it. When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. 3 Remove the accessories. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
The drain pan kit consists of: For installation instructions, see the installation manual of the room ▪ Drain pan thermostat and addendum book for optional equipment. ▪ Installation brackets RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
NOT shown, and are questions first: the responsibility of the installer. ▪ How many rooms are heated (or cooled) by the ROTEX ▪ For more information about the configuration settings to heat pump system? optimize heat pump operation, see "8 Configuration" on...
2 (RT control): Unit operation is decided based on the ambient Benefits ▪ #: [A.2.1.7] temperature of the user interface. ▪ Wireless. The ROTEX external room thermostat is available in a ▪ Code: [C-07] wireless version. Number of water temperature 0 (1 LWT zone): Main zones: ▪...
Example: If the heat pump system is used to heat up one floor under floor heating is shut off by the shut-off valve. where all the rooms have the same heat emitters. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 13
▪ Easy. Same installation as for one room, but with thermostatic valves. Heat pump convectors Setup Main leaving water temperature zone RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ For each room with heat pump convectors: The desired room temperature is set via the remote controller of the heat pump convectors. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ The heat pump convectors are directly connected to the indoor the different heat emitters. unit. ▪ Under floor heating has the best performance with ROTEX ▪ The desired room temperature is set via the remote controller of HPSU. the heat pump convectors for each room.
Page 16
▪ During heating operation of the auxiliary boiler, the ▪ ROTEX is NOT responsible for incorrect or unsafe auxiliary boiler operates to achieve the desired water situations in the auxiliary boiler system. temperature set via the auxiliary boiler controller.
5.4.2 System layout – Standalone DHW tank temperature. However, this consumes more energy. ROTEX Only for RHBH/X. recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.
"8 Configuration" on page 45. ROTEX recommends to heat up the DHW tank during the day. ▪ Connecting the electrical wiring of the standalone DHW tank to ▪ If energy prices are lower during the night, ROTEX the indoor unit, see the installation manual of the DHW tank.
▪ Setup and configuration: To get accurate energy data, measure the capacity (resistance measurement) and set the capacity via the user interface for: ▪ The backup heater (step 1 and step 2) ▪ The booster heater RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ Connect power meter 2 to X5M/9 and X5M/10. Power meter types ▪ Power meter 1: Single- or three-phase power meter according to the power supply of the outdoor unit. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Therefore, the electrical heaters are limited and turned OFF first. The system limits power consumption in the following order: The power or current of the entire ROTEX system is limited dynamically by digital inputs (maximum four steps). Each power Limits certain electrical heaters.
▪ That is NOT exposed to direct sunlight detailed information about spacing guidelines. ▪ If this is NOT possible, ROTEX recommends to connect a remote outdoor sensor (option EKRSCA1). NOTICE ▪ Setup: For installation instructions, see the installation manual of ▪...
Also read the precautions and requirements in the Liquid piping Ø6.4 mm (1/4") "General safety precautions" chapter. Gas piping Ø15.9 mm (5/8") ▪ Mind the measurement guidelines: ▪ Piping temper grade and thickness: RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Use the following graph to determine the maximum water volume for the calculated pre-pressure. Recirculation connection Hot water connection Shower Recirculation pump RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Only a licensed installer may adjust the pre-pressure of the expansion vessel. When changing the default pre-pressure of the expansion vessel (1 bar) is required, take following guidelines into account: Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Whether the power supply is interrupted or not, the wiring to the unit is different. Single power supply for outdoor unit, backup heater and booster heater Backup heater Indoor unit Domestic hot water tank Booster heater RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
500 m. Applicable for both single user interface and dual use interface connection. NOTICE More technical specifications of the different connections 1× are indicated on the inside of the indoor unit. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Protecting the unit against snow and wind by installing a snow recommended to construct a pedestal, and on this pedestal install cover and baffle plates. See "Preparing installation site" in the EKFT008CA option kit. "6 Preparation" on page 22. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Maximum snowfall height EKFT008CA option kit NOTICE The pedestal MUST be aligned with the backside of the U‑beam. 3 Remove the protective cardboard and instruction sheet. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
7.4.1 About mounting the indoor unit U-beams When You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
5× 3 Put the installation pattern (see packing) on the wall and follow the steps as shown below. 2× 4 Lift the unit. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ NEVER install a drier to this R410A unit to guarantee and leaks. its lifetime. The drying material may dissolve and damage the system. Torque wrench Spanner Piping union Flare nut RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ Set the nitrogen pressure to 20 kPa (just enough so it can be felt Silicon sealant, make sure there is no gap. on the skin) with a pressure-reducing valve. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
If there is a possibility of moisture being present in the refrigerant piping (for example, water may have entered the piping), first carry out the vacuum drying procedure below until all moisture has been removed. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Connect the vacuum pump and manifold as follows: ▪ After a leak. Charging additional refrigerant Before charging additional refrigerant, make sure the outdoor unit's external refrigerant piping is checked (leak test, vacuum drying). Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
If a complete recharge is necessary, the total refrigerant Filling the domestic hot water tank. charge is: the factory refrigerant charge (see unit name Insulating the water piping. plate) + the determined additional amount. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
(higher pressure at higher water temperature). However, at all times water pressure shall remain above 1 bar to avoid air entering the circuit. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
"7.9.8 To connect the backup heater power supply" on page 41. 7.9.3 Precautions when connecting the electrical wiring INFORMATION Also read the precautions and requirements in the following chapters: ▪ General safety precautions ▪ Preparation RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
To connect the backup heater power supply CAUTION To guarantee the unit is completely earthed, always connect the backup heater power supply and the earth cable. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 42
During connection of the backup heater, miswiring is possible. To detect possible miswiring, it is highly recommended to measure the resistance value of the heater elements. Depending on the different Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
The main user interface is required for operation, but has to be ordered separately (mandatory option). 4A From the rear 4B From the left 1× 1× RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
1 Connect the changeover to external heat source cable to the S2S S3S appropriate terminals as shown in the illustration below. 2 Fix the cable with cable ties to the cable tie mountings. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
2 Close the service cover. you configure the system. Afterwards. If necessary, you can make changes to the configuration afterwards. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
1 Set the user permission level to Installer. 5 Repeat previous steps if you have to modify other settings. 2 Go to [A]: > Installer settings. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Confirm Adjust Scroll 6 The user interface requests confirmation if you are sure to proceed. Time What is the current time? : 00 Confirm Adjust Scroll RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
The system can heat up or cool down a space. Depending on the type of application, the space heating/cooling settings must be made accordingly. ▪ a: Main LWT zone continued >> Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
This chapter only applies to systems with a domestic hot water tank installed: ▪ RHBH/X: an optional domestic hot water tank is available, ▪ RHVH/X: a domestic hot water tank is standard incorporated into the indoor unit. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 50
Non‑return valve (field supply) Shower (field supply) Cold water INFORMATION The correct domestic hot water default settings becomes only applicable when domestic hot water operation is activated ([E‑05]=1). Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
I/ Range: 0~10 kW (in steps of 0.2 kW) O PCB cannot be used for space heating/cooling output. "5 Application guidelines" on page 10. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
▪ fixed in time (i.e., NOT scheduled) ▪ Weather dep.: The desired leaving water temperature is: ▪ weather-dependent (i.e. depends outdoor ambient temperature) ▪ fixed in time (i.e., NOT scheduled) continued >> Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 53
▪ according schedule. scheduled actions are On or OFF. Remark: This value can only be set in leaving water temperature control. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 54
This results in: ▪ stable room temperatures exactly matching desired temperature (higher comfort level) ▪ less On/OFF cycles (lower noise level, higher comfort and higher efficiency) Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Therefore it is important to set this correctly. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
(= the leaving water temperature zone with the [7.4.2.3] [8-07] Comfort (cooling) lowest leaving water temperature in heating operation and the highest leaving water temperature in cooling operation) [9‑03]~[9‑02]°C (default: 18°C) Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 57
ONLY applicable in room thermostat control and when the R=4°C (−2°C<T <2°C) temperature is displayed in °C. ▪ 3 (enabled) L=2°C, R=8°C (−4°C<T <4°C) ▪ 4 (enabled) L=4°C, R=8°C (−4°C<T <4°C) RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 58
Room frost protection is NOT control ([C‑07]=0) guaranteed. NOTICE If the system does NOT contain a backup heater, do NOT change the default room antifrost temperature. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 59
OFF to avoid NOT guaranteed. However, if [2‑06] is set to "1", limited frost overheating. protection by the unit is possible: RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Code Description [7.4.3.1] [6-0A] 30°C~[6‑0E]°C (default: 60°C) Changeover settings related to the outdoor temperature (ONLY when automatic is selected): Storage eco Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 61
In reheat mode, desired tank temperature weather dependent. Note: When displayed tank temperature is weather dependent, it cannot be adjusted on the user interface. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 62
Range: 5~95 minutes (default: 30) heater is turned OFF. The domestic hot water tank temperature will increase with [7-00] above selected temperature set point. Range: 0°C~4°C (default: 0°C) Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 63
▪ 0: No Hot water request for heat pump (1=request, 0=no request) Time ▪ 1: Yes [8-03]: Booster heater delay timer [A.4.4.3] [2‑02] Start time: 00~23:00, step: 1:00. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
In this way it is possible to limit the backup heater capacity. [5-00] Is backup heater operation allowed above equilibrium temperature during space heating operation? ▪ 1: NOT allowed ▪ 0: Allowed Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 65
50°C, ROTEX recommends NOT to disable the backup heater ▪ [C‑04] Bivalent hysteresis: defines the temperature difference second step because it will have a big impact on the between bivalent ON temperature and bivalent OFF temperature.
5 when bivalent operation function is enabled. outdoor temperature when space ROTEX shall NOT be held liable for any damage resulting heating priority is enabled. The from failure to observe this rule. corrected (higher) set point will make...
Page 67
Defines whether the outdoor unit power supply can be interrupted (internally by indoor unit control) during stand-still conditions (no space heating/cooling nor domestic hot water demand). The final RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 68
20 kW) this functionality. [A.6.3.6.4] [5-0C] Limit DI4 Pwr consumpt. control 0 kW~20 kW, step: 0.5 kW (default: 20 kW) Priority: Only applicable in case of an optional RKHW. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 69
<4°C (pump will be activated for 10 minutes and deactivated after X04+08 and RHVH/X04+08), the setting [4‑01] defines the priority of 10 minutes). ROTEX shall NOT be held liable for any damage the electrical heaters depending on applicable limitation. resulting this functionality.
Tank temperature Quiet level [7.7] Set weather dependent Main [7.7.1] Main Additional Set weather-dependent heating Set weather-dependent cooling [7.7.2] Additional Set weather-dependent heating Set weather-dependent cooling Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings, settings will be visible/invisible. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
(only applicable in case of hybrid system) needed during defrost/backup heater operation. The system is properly earthed and the earth terminals are tightened. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
1 the duration in hours, up to 72 hours, ▪ Alarm output test 2 the desired leaving water temperature. ▪ Cooling/heating signal test Example: ▪ Quick heat-up test ▪ Circulation pump test Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Maintenance and service Screed dryout Current step NOTICE Remaining 14d 12h Desired LWT 25°C Maintenance should preferably be carried out yearly by an installer or service agent. Stop RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Booster heater of the domestic hot water tank INFORMATION Only for wall-mounted units equipped with a domestic hot water tank with a built-in electrical booster heater (RKHW). Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
The preferential kWh rate signal Wait for the power to return (2 was sent by the electricity hours max.). company RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
1 Press the forced cooling operation switch SW1 to begin forced cooling. 2 Press the forced cooling operation switch SW1 to stop forced cooling. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 82
5°C (see temperature read out of the indoor unit). You can achieve this, for example, by activating all fans of the fan coil units. Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Refrigerant suction connection Ø15.9 mm flare connection Pump User interface Safety valve pressure Air purge Expansion vessel Pressure gauge Heat exchanger (refrigerant/water) Stop valve with drain/fill valve (1‑1/4" F BSP) (included accessory) Water filter Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 85
14 Technical data Wire entrance of the power supply/communication wire Service door Switch box terminals Switch box terminals for the domestic hot water tank (option) 3D088485 RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
14 Technical data 14.3 Center of gravity 14.3.1 Center of gravity: Outdoor unit UNIT 4TW60819-1 ERLQ*004=RRLQ004CAV3 ERLQ*006/008=RRLQ006CAV3/RRLQ008CAV3 Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Gives feedback to the interface about the actual flow. Based on this information (and other), the interface adjusts the pump speed. Heat exchanger Water pump Circulates the water in the water circuit. Water filter RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Socket X13A, receives the K3M connector. Main PCB A1P Socket X9A, receives the thermistor connector. (Only for installations with domestic hot water tank) PCB fuse FU1 Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Page 93
14 Technical data Brown Green Orange Purple White Yellow RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 Installer reference guide RRLQ004~008CA + RHBH/X04+08CB ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
See also the minimum and maximum allowed water flow range in the technical specifications. ▪ Water quality MUST be according to EN directive EC98/83EC. RRLQ004~008CA + RHBH/X04+08CB Installer reference guide ROTEX HPSU low temperature Bi‑bloc 4P384979-1 – 2015.01...
Optional equipment Equipment made or approved by ROTEX that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment not made by ROTEX that can be combined with product according instructions accompanying documentation.
Page 102
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C 7.4.1.3 Comfort (cooling)
Page 103
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.2.1.5 [5-0D] BUH type 0: 1P,(1/2) 1: 1P,(1/1+2) 2: 3P,(1/2) 3: 3P,(1/1+2) (*3) 4: 3PN,(1/2) 5: 3PN,(1/1+2) (*4) A.2.1.6 [D-01] Preferential kWh rate 0: No...
Page 104
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) 37~depending on outdoor unit, step: 1°C 55°C A.3.1.2.2.3 [9-07] Temperature range Minimum temp (cooling) 5~18°C, step: 1°C 5°C A.3.1.2.2.4...
Page 105
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.3.2 [4-09] Type 0: Current 1: Power A.6.3.3 [5-05] Amp. value 0~50 A, step: 1 A 50 A A.6.3.4 [5-09] kW value 0~20 kW, step: 0,5 kW...
Page 106
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [2-01] Should the disinfection function be executed? 0: No 1: Yes [2-02] When should the disinfection function start? 0~23 hour, step: 1 hour [2-03] What is the disinfection target temperature? [E-07]≠...
Page 107
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [6-02] What is the capacity of the booster heater? 0~10kW, step: 0,2kW [6-03] What is the capacity of the backup heater step 1? 0~10kW, step: 0,2kW [6-04] What is the capacity of the backup heater step 2?
Page 108
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [A-02] 0 (*5) 1 (*6) [A-03] [A-04] [B-00] [B-01] [B-02] [B-03] [B-04] [C-00] Domestic heating water priority. 0: Solar priority 1: Heat pump priority [C-01] [C-02]...
Page 109
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [E-0B] Is a bi-zone kit installed? 0 (#) [E-0C] [F-00] Pump operation allowed outside range. 0: Disabled 1: Enabled [F-01] Above which outdoor temperature is cooling allowed? 10~35°C, step: 1°C...
Page 112