Rotex RRLQ011CAV3 Installation Manual

Rotex RRLQ011CAV3 Installation Manual

Outdoor unit for air to water heat pump

Advertisement

Installation manual

Outdoor unit for air to water heat pump
RRLQ011CAV3
RRLQ014CAV3
RRLQ016CAV3
                            
RRLQ011CAW1
Installation manual
RRLQ014CAW1
English
Outdoor unit for air to water heat pump
RRLQ016CAW1

Advertisement

Table of Contents
loading

Summary of Contents for Rotex RRLQ011CAV3

  • Page 1: Installation Manual

    Installation manual Outdoor unit for air to water heat pump RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3                              RRLQ011CAW1 Installation manual RRLQ014CAW1 English Outdoor unit for air to water heat pump RRLQ016CAW1...
  • Page 2 (mm) RRLQ — ≥200 A, B, C — ≥200 ≥200 ≥200 B, E — ≥200 ≥1000 ≤500 A, B, C, E — ≥300 ≥300 ≥300 ≥1000 ≤500 — ≥500 D, E — ≥500 ≥1000 ≤500 B, D — ≥200 ≥500 B, D, E <H ≤½H...
  • Page 3 3PW57793-2A...
  • Page 4: Table Of Contents

    ▪ Installer reference guide: Table of Contents ▪ Preparation of the installation, technical specifications, good practices, reference data,… ▪ Format: Digital files on the ROTEX homepage 1 About the documentation ▪ Addendum book for optional equipment: About this document..............▪ Additional info about how to install optional equipment 2 About the box ▪...
  • Page 5: To Install The Outdoor Unit

    4 Installation NOTICE If drain holes of the outdoor unit are covered by a mounting base or by floor surface, raise the unit to provide a free space of more than 150 mm under the outdoor unit. 4× M12 Drain holes Model Bottom view (mm) RRLQ...
  • Page 6: To Determine If Oil Traps Are Required

    4 Installation 6 If the outdoor unit is installed above the indoor unit, cover the stop valves (h, see above) with sealing material to prevent condensed water on the stop valves from moving to the indoor unit. NOTICE Any exposed piping might cause condensation. 7 Reattach the service cover and the piping intake plate.
  • Page 7: To Perform Vacuum Drying

    4 Installation NOTICE 4.4.2 To charge refrigerant Make sure to use a recommended bubble test solution WARNING from your wholesaler. Do not use soap water, which may cause cracking of flare nuts (soap water may contain salt, ▪ Only use R410A as refrigerant. Other substances may which absorbs moisture that will freeze when the piping cause explosions and accidents.
  • Page 8: About Electrical Compliance

    Interconnection cable with a short-circuit power S greater than or equal to the Power supply cable minimum S value. Earth leakage circuit breaker Fuse Model Minimum S value RRLQ011CAV3 0.22 Ω 525 kVA RRLQ014CAV3 RRLQ016CAV3 RRLQ_W1 Equipment complying with EN/IEC  61000‑3‑12 (European/...
  • Page 9: To Reposition The Air Thermistor On The Outdoor Unit

    5 Starting up the outdoor unit Routing through Choose one of the 3 possibilities: the frame a Power supply, earth wiring, and bottom plate heater wire (if applicable) b Interconnection cable Connecting to the When cables are routed from the unit, a frame protection sleeve for the conduits (PG insertions) can be inserted at the knockout...
  • Page 10: Technical Data

    6 Technical data Technical data Latest information can be found in the technical engineering data. Service space: Outdoor unit Single unit ( ) | Multiple units ( See figure 1 on the inside of the front cover. A,B,C,D Obstacles (walls/baffle plates) Obstacle (roof) a,b,c,d,e Minimum service space between the unit and obstacles A, B, C, D and E...
  • Page 11 6 Technical data Q1DI Earth leakage circuit breaker (field supply) R1~R4 Resistor Thermistor (air) Thermistor (discharge) Thermistor (suction) Thermistor (heat exchanger) Thermistor (heat exchanger middle) Thermistor (liquid) Thermistor (fin) (RRLQ_W1) R10T Thermistor (fin) (RRLQ_V3) Signal receiver circuit (RRLQ_V3) S1NPH Pressure sensor S1PH High pressure switch Signal transmission circuit...
  • Page 12 Sede operativa Via Milano, 6 - 20097 San Donato Milanese MI-Italy Tel. +39 02 51619.1 · Fax +39 02 51619222 e-mail info@rotexitalia.it · www.rotexitalia.it Numero verde ROTEX 800-886699 ROTEX ROTEX Heating Systems SARL Représenté en France par: 1, rue des Artisans ·...