16.6. Analog Input Objects

Optional Properties Supported:
Optional Writable Properties:
Object ID
198
199
200*
201*
202*
203*
204*
205*
206*
207*
208*
209*
210*
231
232
239
240
241
242
Local Outside Air Temperature
243
244
245
246
247
248
250
252
Space Temperature Set Point (Effective)
253
254
255
256
257
258
259
260
261
262
263
None
Out_Of_Service (AI239 - AI252, AI274 - AI285 only)
Table 43. Analog Input Objects List
Object Name
Mac Address
IMC Address
IMC Version[4]
IMC Version[5]
IMC Version[6]
IMC Version[7]
IMC Version[8]
IMC Version[9]
IMC Version[10]
IMC Version[11]
IMC Version[12]
IMC Version[13]
IMC Version[14
Unit ID
Unit Status
Space Temperature
Discharge Air Temperature
Effective Occupancy
Local Space Temperature
Outside Air Damper
Heat Primary
Heat Secondary
Cool Primary
Economizer Enabled
Supply Fan Status
Current Error
Error Pointer
Most Recent Error 1
Most Recent Error 2
Most Recent Error 3
Most Recent Error 4
Most Recent Error 5
Most Recent Error 6
Most Recent Error 7
Most Recent Error 8
Most Recent Error 9
Units
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
Deg. F
Deg. F
None
Deg. F
Deg. F
Percent
Percent
Percent
Percent
Percent
Percent
Deg. F
None
None
None
None
None
None
None
None
None
None
None
70
Data Range
0 − 127
1−31
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 127
0 − 255
63.75 − 100.00
−8.7 – 164.4
0 − 2
−30.6 – 131.6
63.75 – 100.00
0 − 100, 255
0 – 100
0 – 100
0 – 100
0, 1, 255
0 − 100
40 – 95
0 − 255
0 – 83
1 − 255
1 − 255
1 − 255
1 − 255
1 − 255
1 − 255
1 − 255
1 − 255
1 − 255