Mitsubishi FX2N-16LNK-M User Manual page 15

Melsec-i/o link remote i/o system master block
Table of Contents

Advertisement

FX
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
2N
Performance specifications
Specifications item
Maximum number of con-
trolled I/O points
I/O refresh time
Communication speed
Communication method
Synchronization method
Error control method
Transmission path
type
Transmission distance Maximum total extension distance: 200 m
Maximum number of
connected units
Error (RUN) indication/out-
put
Number of occupied I/O
points
Supply voltage from outside 21.6 to 27.6V DC (for communication path)
Current consumption of
power supply from outside
Current consumption inside
(5 VDC)
Weight
128 points (16 remote units with 4 points each) per master block
Approx. 5.4 ms (without regard to number of I/O points)
38400 bps
Register insertion method
Frame synchronization and bit synchronization used together
Adjacent phase inversion check and parity check used together (retry by
timeout)
Bus (multi-drop) type (T branches are available. Terminal resistors are not
required.)
16 stations per master block
Indication by LEDs
Confirmation of 24V DC power supplied from outside to master block by
M8009 (24V DC down) in basic unit
External outputs by RUNA and RUNB
Selectable among 16, 32, 48, 64, 96 and 128
90 mA (TYP 24V DC)
200 mA
0.5 kg
Product Specifications 2
Description
2-5

Advertisement

Table of Contents
loading

Table of Contents