Types of load

Operating
Load for
cycle
converter
DC I
I
continuous (I
DC I
DC II
I
for 15 min and
DC II
1,5 * I
for 60 s
DC II
DC III *
I
for 15 min and
DC III
1,5 * I
for 120 s
DC III
DC IV *
I
for 15 min and
DC IV
2 * I
for 10 s
DC IV
* Load cycle is not identical to the menu item Duty cycle in the DCSize program !
The example load cycle show one case of DC standard
Table 2.3/2: Definition of the load cycles
If the driven machine’s load cycle does not
correspond to one of the examples listed, you
can determine the necessary power converter
DCSize
using the
software program.
This program can be run under Microsoft
dows, and enables you to dimension the motor
and the power converter, taking types of load
(load cycle), ambient temperature, site elevation,
etc. into account. The design result will be
presented in tables, charts, and can be printed out
as well.
To facilitate the start-up procedure as much as
possible, every power converter has been pro-
vided with a current measuring feature, which
can be adjusted to the high current required by
means of software parameters.
Typical applications
)
pumps, fans
dN
extruders, conveyor belts
extruders, conveyor belts
®
Win-
Fig. 2.3/1: Entry mask on the computer screen for the dimensioning program DCSize.
Microsoft is a registered trademark. Windows is a designation of the Microsoft Corporation.
Load cycle
100%
Ã
15 min
150% 100%
Ã
Ã
15 min
150% 100%
Ã
15 min
200% 100%
II F 2-7