4222 Process Parameter List - PR 4222 Configuration Manual

Universal i/f converter/modbus rtu
Hide thumbs Also See for 4222:
Table of Contents

Advertisement

Parameter
Register
No.
Name
Address
DISPLAY VALUE
0
1000
PERCENT PV
1
1002
MEASURE
2
1003
STATUS
ERROR STATUS
3
1004
PRIMARY RAW
5
1005
VALUE
PRIMARY VALUE
6
1007
RELATIVE PV
7
1009
OUTPUT
8
1011
FREQUENCY
MEASURE
9
1013
CONTROL
TIMEOUT
10
1014
COUNTER
INTERNAL
11
1015
TEMPERATURE

4222 Process Parameter List

Register
Read/
Type
Size
Write
2
RO
INTEGER
1
RO
INTEGER
1
RO
INTEGER
1
RO
INTEGER
2
RO
FLOAT
2
R/W
FLOAT
2
RO
FLOAT
2
R/W
FLOAT
1
R/W
INTEGER
1
R/W
INTEGER
1
RO
INTEGER
Description
The measured value in 1/10 of °C/°F for
temperature Input types, or the scaled
display value for non-temperature input types
(INTEGER version of PRIMARY VALUE)
The relative input value as 1/100 of %
calculated from PRIMARY VALUE.
For temperature input types 0...100%
corresponds the selected temperature range
(OUTPUT LOW...OUTPUT HIGH)
For non-temperature input types 0...100%
corresponds the selected fixed range
(e.g. 4...20 mA)
The actual measurement status
The actual error status (Device errors)
The measured value in 1/10 of °C/°F for
temperature Input types, or the scaled
display value for non-temperature input types,
NOT PROCESS CALIBRATED.
The measured value in 1/10 of °C/°F for
temperature Input types, or the scaled display
value for non-temperature input types
The relative input value calculated
from PRIMARY VALUE.
For temperature input types relative to
selected temperature range
(OUTPUT LOW...OUTPUT HIGH)
For non-temperarure input types relative to
selected fixed range (e.g. 4...20 mA)
Calculated output value in mHz or 1/1000nds
of pulses per min./hour/day
Measurement control.
By disabling update of certain READ/WRITE
parameters PRIMARY VALUE, OUTPUT VALUE or
RELAY STATUS, these can be simulated
by writing values.
All bits are cleared when
TIMEOUT COUNTER reaches 0
Time out counter,
decrements every 0.075 second.
When reaching 0 (if not refreshed) all bits in
MEASURE CONTROL will be cleared.
Internal measured or connector temperature
in 1/10 of °C/°F
4222MCM101
Values
Range for non-temperature input types:
DISPLAY LOW...DISPLAY HIGH
Range for temperature input types: equals
the measurement range for the
selected sensor type
Range: 0...9999
(e.g. 7898 = 78.98%)
OUTPUT UNDERRANGE:
OUTPUT OVERRANGE:
1
OUTPUT LOW LINITED:
1
OUTPUT HIGH LIMITED:
1
INPUT UNDERRANGE:
1
INPUT OVERRANGE:
1
SENSOR SHORTED:
1
SENSOR BROKEN:
1
AD COMM. ERROR
1
CJC ERROR
1
RAM ERROR
1
EEP ERROR
1
FLASH ERROR
1
NOT CALIBRATED
1
BAD OUTPUT
1
NO OUTPUT
1
OUTPUT SUPPLY ERROR
1
INPUT SUPPLY ERROR
1
Range for non-temperature input types:
DISPLAY LOW...DISPLAY HIGH
Range for temperature input types equals
the measurement range for the selected
sensor type
Range for non-temperature input types:
DISPLAY LOW...DISPLAY HIGH
Range for temperature input types equals
the measurement range for the selected
sensor type
Range:
0.0...1.0
Range with frequency selected:
0...25000000 (0...25000 Hz)
Range with pulse selected:
0...30000000
RESTART SCAN
bit 0 = 1
RESTART WITH
NEW CONFIGURATION bit 1 = 1
DISABLE PRIMARY
VALUE UPDATE
bit 2 = 1
DISABLE OUTPUT
VALUE UPDATE
bit 3 = 1
NOT USED
bit 4 = 1
DISABLE
CONFIGURATION CHECK
bit 5 = 1
GET NEW
CONFIGURATION
bit 6 = 1
Range:
0...255
Range:
-200...800 (-20.0...80.0 °C) or
-40...1760 (-4.0...176.0 °F)
bit 0=1
bit 1=
bit 2=
bit 3=
bit 4=
bit 5=
bit 6=
bit 7=
bit 0=
bit 1=
bit 2=
bit 3=
bit 4=
bit 5=
bit 6=
bit 7=
bit 8=
bit 9=
5