Symptom
Reading erratic
Reading response
slow
Reads correctly but
occasionally reads
high when vessel is
not full
Level reading lower
than actual material
level
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC
Cause
echo confidence weak
liquid surface vortexed
material filling
Fill Rate (2.3.8.2.) setting
incorrect
detecting close range echo
build up near top of vessel or
nozzle
nozzle problem
material is within Near Range
zone
multiple echoes processed
vessel near empty and low
dK material
Action
refer to Confidence (2.5.9.1.)
use Auto False Echo Suppression (2.5.10.1.) and Auto
False Echo Suppression Range (2.5.10.2.)
use foam deflector or stillpipe
decrease Fill Rate (2.3.8.2..)
relocate device to side pipe
increase confidence threshold in Echo Threshold (2.5.7.3.)
Re-locate SITRANS LR250
increase measurement response if possible
clean the antenna
use Auto False Echo Suppression (2.5.10.1.) and Auto
False Echo Suppression Range (2.5.10.2.)
decrease Near Range (2.5.1.) (minimum value depends on
antenna type)
raise SITRANS LR250
ensure Algorithm (2.5.7.1.) is set to tF (First echo)
ensure Material (1.2.) selection is LIQUID LOW DK
set Position Detect (2.5.7.2.) to Hybrid
check the setting for CLEF Range (2.5.7.4.): see the table
below Propogation Factor (2.5.3.) for recommended
settings
Diagnosing and troubleshooting
10.4 Operation troubleshooting