Remote operation
7.1 Operating via SIMATIC PDM
Simulate output
1. Open the menu Device – Simulation, select function block 1 or 2, and click on the tab
Simulation (Output).
2. Select Manual Mode (from options AUTO, Manual, or Out of Service) and click on Transfer.
3. Enter simulated value and click on Transfer.
4. After simulation is complete, return to Simulate Output, reselect AUTO mode, and click on
Transfer.
94
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC