Siemens SITRANS LR250 Operating Instructions Manual page 72

Radar transmitters profibus pa
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Commissioning
6.3 Application examples
Parameter type
Quick Start
Wizard
parameters
Independent
parameters
Return to Measurement: press Mode
70
Sensor reference point
0.5 m
High calibration point
3.5. m
Low calibration point
Parameter No./Name
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Operating Mode (1.5.)
Low Calibration Point (1.6.)
High Calibration Point (1.7.)
Apply? (Apply changes) (1.8)
Vessel Shape (2.4.1.1.)
Maximum Volume (2.4.1.2.)
Vessel Dimension A (2.4.1.3.)
Vessel Dimension L (2.4.1.4.)
LOE Timer (2.3.6.)
Mode (2.6.9.1.)
Value (2.6.9.2.)
A = 0.8 m
L = 6 m
100% = 8000 L
Volume reading
Options/
Values
LIQUID
MED
M
LEVEL
3.5
0.5
YES
PARABOLIC
ENDS
8000
0.8
6
2
Substitute value User-defined value to be
4.5
to start normal operation.
Operating Instructions, 08/2014, A5E32221386-AC
Function
Medium =1 m/minute
meters
Level is reported as
Volume when a vessel
shape is selected.
3.5 m (11.48 ft)
0.5 m (1.64 ft)
Transfers Quick Start
settings to device.
Defines vessel shape.
8000 liters
0.8 m (2.62 ft)
6 m (19.68 ft)
2 minutes
used.
4.5 m (14.76 ft)
SITRANS LR250 (PROFIBUS PA)