4. Installation
4.9
Installing the outside sensor
28
4.9.1.
It is important to select a place that allows the sensor to measure the
outside conditions correctly and effectively.
Advised positions:
4 on one face of the area to be heated, on the north if possible
4 half way up the wall in the room to be heated
4 under the influence of meteorological variations
4 protected from direct sunlight
4 easy to access
Recommended position
A
Possible position
B
Inhabited height controlled by the sensor
H
Inhabited area controlled by the sensor
Z
8800N001-C
Positions to be avoided:
4 masked by a building element (balcony, roof, etc.)
4 close to a disruptive heat source (sun, chimney, ventilation grid,
etc.)
8800N002-C
4.9.2.
Mount the sensor using the screws and dowels provided.
Choice of the location
Installing the outside sensor
MCA 15 - MCA 25 MCA 25/28 MI
29/04/2010 - 300022146-001-B