1MRS756740
3.10.3.
COM600 series, Version 4.1
HMI Configuration Manual

Configuring event definitions

You can configure event definitions in SAB600. Event definitions specify the type of
events that are created for HMI event and alarm lists. You can specify whether an event
appears only on the event list, on both event and alarm lists, or whether it is displayed
at all. You can also add event texts for the events and specify whether alarms must be
acknowledged by the user.
Event definitions are linked to data objects by configuring the event properties available
for data objects. When importing IED configurations from connectivity packages or IED
SCL description files, event definitions are linked to data objects by default. For example
switch position data object CSWIx.Pos is linked by default to switch position event
definition. The default linking rules are specified in a DOParamsDefaults.xml file located
in the \Program files\ABB\COM600\bin\Tools\SCLImport in the computer where SAB600
is installed.
To configure event definitions:
1. Select the event you want to configure in the object tree.
2. The object properties appear now in the Object Properties window, see Figure 3.10.3-
1.
3. You can assign the event with parameter values.