Disturbance Data Upload - ABB com600 Configuration Manual

Hide thumbs Also See for com600:
Table of Contents

Advertisement

3.13.
50
COM600 series, Version 4.1
HMI Configuration Manual
Figure 3.12-4 Exporting XML file
Importing parameters
With the Import function it is possible to import an existing Parameter Filtering Tool
configuration for example from another computer. An XML file created with the Para-
meter Filtering Tool can be imported into another device or project using this tool.

Disturbance data upload

The basic support for the disturbance data upload (data upload and conversion to
COMTRADE format) is implemented to each OPC Server. Protocol and device-specific
differences are hidden from the OPC client. The files are stored temporarily to the
COM600 computer, where they can be transferred further using for example ftp. COM600
has a possibility to activate the disturbance data upload from the IED and to receive the
file into the computer where HMI is run.
If the IED and the OPC server used for communication support disturbance data upload,
the properties for configuring the function can be found from the corresponding OPC
server user's manual, see 1.10, Related documents.
1MRS756740