Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
Parameter
...Input/Output
Current Output 1
Source
% Oxygen
Temperature
Cell mV
Type
Linear
Log. Two Decades
Log. Three Decades
Eng. Range Hi
Oxygen
Temperature
mV
Eng. Range Lo
Oxygen
Temperature
mV
*The Endura AZ30 oxygen systems must be used only for measuring non-oxygen enriched gasses (not more than 21 %
oxygen [air]) at pressure no greater than 1.1 bar absolute (44 in. WG). Operating the system in oxygen-enriched
atmospheres will invalidate / compromise certification.
Table 6.12 Input/Output Menu (Continued)
62
Comment / [Range]
Selects the parameter to be retransmitted by the
current output.
Selects a linear or logarithmic output.
Note. Displayed only when Source is set to
% Oxygen.
Selects an engineering range high value, depending
on the option selected in Source.
[0.00 to 100.00 % O
*]
2
[–200 to 1800 °C (–328 to 3272 °F)]
[–100.0 to 400.0 mV]
Selects an engineering range low value depending on
the option selected in Source.
Note. Not enabled if Type = Log Two Decades or
Log Three Decades.
[0.00 to 100.00 % O
*]
2
[–200 to 1800 °C (–328 to 3272 °F)]
[–100.0 to 400.0 mV]
6 Programming
Default
% Oxygen
Linear
25.00 %O2
0.25 %O2
COI/AZ30E–EN Rev. D