Table 18 Recommended Conduit And Cable Sizes For Use With 100% Rated Breakers - Liebert EXL Installation Manual

625-1200kva, 1.0pf, 60hz, three-phase, single-module and multi-module
Table of Contents

Advertisement

Table 18
Recommended conduit and cable sizes for use with 100% rated breakers
Rectifier Input
UPS Rating
Voltage
kVA
kW
VAC
625
625
750
750
480
800
800
1000
1000
1100
1100
480
1200
1200
Bypass Input
Voltage
UPS Rating
VAC
kVA
kW
625
625
750
750
480
800
800
1000
1000
1100
1100
480
1200
1200
Output
UPS Rating
Voltage
kVA
kW
VAC
625
625
750
750
480
800
800
1000
1000
1100
1100
480
1200
1200
Vertiv
| Liebert® EXL™ 625-1100kVA Installation Manual
(# of conduits); size of conduits; # -size of phase cables per conduit;
Cable
Entry
Copper Conductors
Top
(3) 2.5"C 3-350kcmil; #2/0AWG
Bottom
(3) 3"C 3-350kcmil; #2/0AWG
Top
(3) 3"C 3-500kcmil; #2/0AWG
Bottom
(3) 3.5"C 3-500kcmil; #2/0AWG
Top
(4) 2.5"C 3-350kcmil; #3/0AWG
Bottom
(4) 3"C 3-350kcmil; #3/0AWG
Top
(4) 3"C 3-500kcmil; #4/0AWG
Bottom
(4) 3.5"C 3-500kcmil; #4/0AWG
Top
(5) 3"C 3-500kcmil; #4/0AWG
Bottom
(5) 3.5"C 3-500kcmil; #4/0AWG
Top
(5) 3"C 3-500kcmil; #4/0AWG
Bottom
(5) 3.5"C 3-500kcmil; #4/0AWG
(# of conduits); size of conduits; # - size of phase cables per conduit;
Cable
Entry
Copper Conductors
Top
(3) 2.5"C 3-350kcmil; #1/0AWG
Bottom
(3) 3"C 3-350kcmil; #1/0AWG
Top
(3) 3"C 3-500kcmil; #2/0AWG
Bottom
(3) 3.5"C 3-500kcmil; #2/0AWG
Top
(3) 3"C 3-500kcmil; #2/0AWG
Bottom
(3) 3.5"C 3-500kcmil; #2/0AWG
Top
(4) 3"C 3-500kcmil; #4/0AWG
Bottom
(4) 3.5"C 3-500kcmil; #4/0AWG
Top
(4) 3"C 3-500kcmil; #4/0AWG
Bottom
(4) 3.5"C 3-500kcmil; #4/0AWG
Top
(5) 3"C 3-500kcmil; #4/0AWG
Bottom
(5) 3.5"C 3-500kcmil; #4/0AWG
(# of conduits); size of conduits; # -size of phase cables per conduit;
Cable
Entry
Copper Conductors
Top
(3) 2.5"C 3-350kcmil; #1/0AWG
Bottom
(3) 3"C 3-350kcmil; #1/0AWG
Top
(3) 3"C 3-500kcmil; #2/0AWG
Bottom
(3) 3.5"C 3-500kcmil; #2/0AWG
Top
(3) 3"C 3-500kcmil; #2/0AWG
Bottom
(3) 3.5"C 3-500kcmil; #2/0AWG
Top
(4) 3"C 3-500kcmil; #4/0AWG
Bottom
(4) 3.5"C 3-500kcmil; #4/0AWG
Top
(4) 3"C 3-500kcmil; #4/0AWG
Bottom
(4) 3.5"C 3-500kcmil; #4/0AWG
Top
(5) 3"C 3-500kcmil; #4/0AWG
Bottom
(5) 3.5"C 3-500kcmil; #4/0AWG
size of cable for ground per conduit
Aluminum Conductors
(3) 3"C 3-500kcmil; #4/0AWG
(3) 3.5"C 3-500kcmil; #4/0AWG
(3) 3"C 3-600kcmil; #4/0AWG
(3) 3.5"C 3-600kcmil; #4/0AWG
(4) 3"C 3-500kcmil; 250kcmil
(4) 3.5"C 3-500kcmil; 250kcmil
(5) 3"C 3-500kcmil; 350kcmil
(5) 3.5"C 3-500kcmil; 350kcmil
(5) 3"C 3-600kcmil; 350kcmil
(5) 4"C 3-600kcmil; 350kcmil
(5) 3"C 3-600kcmil; 350kcmil
(5) 4"C 3-600kcmil; 350kcmil
size of cable for ground per conduit
Aluminum Conductors
(3) 3"C 3-500kcmil; #3/0AWG
(3) 3.5"C 3-500kcmil; #3/0AWG
(3) 3"C 3-600kcmil; #4/0AWG
(3) 3.5"C 3-600kcmil; #4/0AWG
(3) 3"C 3-600kcmil; #4/0AWG
(3) 3.5"C 3-600kcmil; #4/0AWG
(5) 3"C 3-500kcmil; 350kcmil
(5) 3.5"C 3-500kcmil; 350kcmil
(5) 3"C 3-500kcmil; 350kcmil
(5) 3.5"C 3-500kcmil; 350kcmil
(5) 3"C 3-600kcmil; 350kcmil
(5) 4"C 3-600kcmil; 350kcmil
size of cable for ground per conduit
Aluminum Conductors
(3) 3"C 3-500kcmil; #3/0AWG
(3) 3.5"C 3-500kcmil; #3/0AWG
(3) 3"C 3-600kcmil; #4/0AWG
(3) 3.5"C 3-600kcmil; #4/0AWG
(3) 3"C 3-600kcmil; #4/0AWG
(3) 3.5"C 3-600kcmil; #4/0AWG
(5) 3"C 3-500kcmil; 350kcmil
(5) 3.5"C 3-500kcmil; 350kcmil
(5) 3"C 3-500kcmil; 350kcmil
(5) 3.5"C 3-500kcmil; 350kcmil
(5) 3"C 3-600kcmil; 350kcmil
(5) 4"C 3-600kcmil; 350kcmil
| Rev. 3 | 02/17