Figure 30 Control Wiring, Programmable Relay Board; Table 12 Programmable Relay Board Pinout - Liebert EXL Installation Manual

625-1200kva, 1.0pf, 60hz, three-phase, single-module and multi-module
Table of Contents

Advertisement

Figure 30
Control wiring, Programmable Relay Board
P99
P66
1.
Customer control wiring connection points are Terminals 1 through 12.
2.
Programmable Relay Board option includes eight signal channels with one Form-C dry contact per channel (see Table 12).
3.
All control wiring (by others) must be run separate from power wiring.
4.
Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A
5.
Maximum cable length is 500 ft. (152m) with #16AWG and flexible stranded cable.
6.
All wiring must be in accordance with national and local electrical codes.
Table 12
Programmable Relay Board pinout
Terminal
Block
Channel
Pin No.
CH1
1-3
CH2
4-6
J71
CH3
7-9
CH4
10-12
CH5
1-3
CH6
4-6
J72
CH7
7-9
CH8
10-12
Vertiv
| Liebert® EXL™ 625-1100kVA Installation Manual
1 2 3 4 5 6 7 8 9 10 11 12