Figure 24 Output And Bypass Terminal Detail, 625-800Kva Liebert Exl Ups, Sms And 1+N; Multi-Module Unit - Liebert EXL Installation Manual

625-1200kva, 1.0pf, 60hz, three-phase, single-module and multi-module
Table of Contents

Advertisement

Figure 24
Output and bypass terminal detail, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
2.36"
(60mm)
2.36" (60mm)
Typ.
#5 Phase Output Busbar 17.7 X 4 X .25
2.36"
(60mm)
Typ.
2.36" (60mm)
Typ.
#6 Output Ground Busbar 25.4 x 3 x .25
1.97"
(50mm)
Typ.
Notes:
1. Control wiring and power wiring must be run in separate conduits
2. All wiring is to be in accordance with national and local electrical codes.
3. See Page 1, Drawing U46-8E-3200A and Page 2, Drawing U46-8E-3200B.
4. Based on NEC 408.56 minimum spacing, all live parts, including lugs,
must be at least 1" (25mm) from any other live part from a different phase
or the chassis frame. If lug stacking is required, the method of stacking
and required minimum spacing is the responsibility of the installing
contractor and authority having jurisdiction.
Vertiv
| Liebert® EXL™ 625-1100kVA Installation Manual
#4 Bypass Input Busbar 38.2 x 4 x .25
Typ.
Ø .56" (14mm) Typ.
1.44" (37mm)
1.0" (25mm) Typ.
Ø .56" (14mm) Typ.
Ø .56" (14mm) Typ.
6
5
1.75" (44mm)
18.5"
(469mm)
RIGHT SIDE VIEW
OUTPUT/BYPASS
Dual Hole Lug
U46-8E-3200C
Pad Width (Max.)
Rev. 3
1.75" (44mm)
| Rev. 3 | 02/17
1.43" (36mm)
4
58.4"
(1484mm)
30.3"
(770mm)
37