Secondary Menu; Heater Power; Set-Point Voltage - Fluke 9150 User Manual

Portable furnace
Hide thumbs Also See for 9150:
Table of Contents

Advertisement

8.5 Secondary Menu

Functions which are used less often are accessed within the secondary menu.
The secondary menu is accessed by pressing "SET" and "EXIT" simultaneously
and then releasing. The first function in the secondary menu is the heater power
display. (See Figure 4.)

8.6 Heater Power

The temperature controller controls the temperature of the furnace by pulsing the
heater on and off. The total power being applied to the heater is determined by
the duty cycle or the ratio of heater on time to the pulse cycle time. By knowing
the amount of heating the user can tell if the calibrator is heating up to the set-
point, cooling down, or controlling at a constant temperature. Monitoring the
percent heater power lets the user know how stable the well temperature is. With
good control stability the percent heating power should not fluctuate more than
±1% within one minute.
The heater power display is accessed in the secondary menu. Press "SET" and
"EXIT" simultaneously and release. The heater power is displayed as a percent-
age of full power.
 
  
To exit out of the secondary menu press "EXIT". To continue on to the set-point
voltage setting function press "SET".

8.7 Set-point Voltage

The set-point voltage is displayed for informational purposes and is used to
calibrate the instrument.
The value of the set-point voltage changes when the set-point temperature is
changed and also when DC1 and DC2 are adjusted.
  
  
To exit out of the secondary menu, press "EXIT". To continue on to the
proportional band setting function press "SET".
Find Quality Products Online at:
Well temperature
+
Access heater power in secondary menu
Heater power in percent
+
Access heater power in secondary menu
Heater power in percent
Access set-point voltage
Set-point voltage in millivolts
GlobalTestSupply
www.
Controller Operation
8.5
Secondary Menu
.com
sales@GlobalTestSupply.com
8
8-9