9150
User's Guide
Press "SET" to continue. Pressing "EXIT" causes any changes made to the
parameter to be discarded.

8.4.3 Program Set-Points

The controller allows the user to adjust up to eight program points. These are
accessed by pressing "SET" after setting the number of program points as de-
scribed in Section 8.4.2. Each program point has three associated parameters:
the program set-point, the program scan rate, and the program hold (or soak)
time. After adjusting the number of program points press "SET".

Use the "UP" or "DOWN" buttons to select any of the program points. The
controller only allows the user to edit program points that are less than or equal
to the number of programs points selected as explained in Section 8.4.2. For
example, if the user has selected 4 program points program points 5, 6, 7, and 8
cannot be edited.

Press "SET" to edit a program point.
The first value to edit is the program set-point.
0962.7
Use "UP", "DOWN", and "SET" to adjust the set-point as each digit flashes.
 
Press "SET" to save the new set-point value or "EXIT" to discard changes.
The next value to edit is the program soak time.

8-6
Find Quality Products Online at:
Accept the new number of program points.
Program point 1
Program point 4
Edit program point
Program set-point value in °C
New program set-point value for program point 4
Accept the program point set-point
Program point 4 soak time