■ Standard Connection Diagram
The standard connection diagram of 7200MA is shown in Fig. 2. The sign ◎
indicates the main circuit terminal and the sign ○ indicates control circuit terminal.
The terminal function and arrangement are summarized in Table 1 and Table 2. There
are three types of control board, the terminal arrangement is shown as below.
(A) For Compact Size Type 220V : 1-2HP, 440V : 1-2HP
•JNTMBGBB□□□□JKS-1
•JNTMBGBB□□□□JKSU1
Main Ckt
Power Supply
FWD/STOP
REV/STOP
External Fault
Fault RESET
Multi-Step
Speed Ref.1
Multi-Step
Speed Red.2
Jogging
Acc. & Dec.
Switch
0 ~ +10V
2kΩ
1/2W
4 ~ 20 mA
0 ~ +10V
0V
EXTERNAL PG
DC VOLTAGE
PG INPUT
(A PHASE)
Shield
(*1)
Wire
(*2) The terminal arrangement
(*3) The control board code No. : 4P101C0040001
(*4) The CN2 wire code No. : 4H339D0250001
MC
NFB
R/L1
S/L2
T/L3
1
("Close":FWD)
FWD
2
REV
("Close":REV)
3
Eb
4
RESET
5
6
Multi-Function
7
Contact Input
8
SC (DG)
Digital signal Common
E
Shield Sheath
+12V Power Supply for
Speed Ref.
VIN Master Speed Ref. 0 ~ 10V, (20kΩ )
AIN Master Speed Ref.
P
P
AUX Multi-Funtion
Analog Input
P
GND Analog signal Common
(*1)
CN2
(*4)
TP1
1
IP12
IG12
2
A(+)
3
A(-)
4
Shielded
P
Twisted Wire
SC
1
3
E
2
Fig. 2-a Standard connection diagram
•JNTMBGBB□□□□AZS-1
•JNTMBGBB□□□□AZSU1
Braking Resistor
B1/P
B2
Analog
Output 1
Analog
Output 2
(+12V, 20 mA)
4 ~ 20 mA, (250Ω)
0 ~ 10V, (20kΩ )
OPEN
IP12
PULL UP
VIN AIN AUX DO1 DO2 DOG
5
7
4
6
8
+12V
GND
GND
AO1 AO2
9
U/T1
V/T2
IM
W/T3
E
Grounding Lead
(<100 Ω)
AO1
AO2
Analog Monitor 1, 2
(DC 0 ~ 10 V)
GND
RA
Multi-Function Contact Output
RB
250V AC, <1A
30V DC,
<1A
RC
DO1
DO2
Multi-Function Output 1, 2
(Open Collector 48V, 50mA)
DOG
S(+)
RS-485 Port
S(-)
S(-)
S(+)
E
RA RB RC
Need help?