Test Voltage - Siemens PSU300B Manual

Sitop power supply
Table of Contents

Advertisement

Safety, approvals, EMC

7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals and PE together
Test (C)
● Connect the output terminals with one another and measure with respect to PE
Table 7- 1
Test voltage
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
60
Test voltage without auxiliary contact diagram
Test time
Prim ↔ sec (A)
60 s
4200 VDC
60 s
3000 VAC
1 s
2200 VDC
1 s
1500 VAC
1 s
2200 VDC
1 s
1500 VAC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 VDC
700 VDC
1500 VAC
500 VAC
2200 VDC
500 VDC
1500 VAC
350 VAC
2200 VDC
500 VDC
1500 VAC
350 VAC
Manual, 11.2014, C98130-A7574-A2-2-7629
SITOP PSU300M/300B