Ambient conditions

Ambient temperature
Transport and storage temperature
Humidity class
Mechanical stressing
during operation
SITOP PSU300M/300B
Manual, 11.2014, C98130-A7574-A2-2-7629
6EP1436-3BA10 (24 V/20 A)
6EP1424-3BA00 (12 V/20 A)
6EP1436-3BA20 (24 V/17 A)
6EP1437-3BA20 (24 V/30 A)
-25°...+70° C with natural convection
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
-40 ...+85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Climatic class 3K3 according to EN 60721, without condensation
Tested according to:
EN 60068-2-6 vibration, test Fc:
0.075 mm deflection in the range 10 ... 58 Hz
1 g acceleration in the range 58 ... 150 Hz
EN 60068-2-27 shock, test Ea: Acceleration 150 m/s
6EP1456-3BA00 (48 V/10 A)
-10 ...+70° C with natural convection
, test duration 11 ms
2
8
63