Delta DPS-400K User Manual page 105

Dps series three phase 300/400/500 kva
Hide thumbs Also See for DPS-400K:
Table of Contents

Advertisement

1
Switch off the Input Switch (Q1) and the Output Switch (Q4) of the UPS that you
just turned off and turn off all of its connected external battery cabinets' breakers
or fuses. After that, the Bypass AC Source LED
and the Output Switch LED
LOAD NOT POWERED
BYPA.
MAIN
PRESS
2
process, the Inverter Start-up LED
discharging, the Inverter Start-up LED
3
Switch off the Bypass Switch (Q2) of the UPS that you turned off and all of its
connected external battery cabinets' circuit breakers or fuses. After that, all LEDs
are off and no screen appears on the LCD.
NOTE:
If you need to turn off the remaining parallel UPSs, please repeat the
procedures above.
2. If the total critical loads exceed the remaining parallel UPSs' total capacity, all
parallel UPSs' inverters will shut down, inverter static switches will automatically turn
off, and all parallel UPSs will transfer to bypass mode. The total critical loads will be
shared equally by all parallel UPSs, and each of the parallel UPSs has the status of
the LCD and LEDs as follows.
are off and the LCD shows the following screen.
UNI T : # 1 . 1
2010 - 06 - 01
11 : 59 : 59
TO BROWSE EVENT
(004)
7-25
, the Main AC Source LED
shuts off.
7
UPS Operation