Device Object; Mbox - WEG bacnet CFW701 User Manual

Hide thumbs Also See for bacnet CFW701:
Table of Contents

Advertisement

Object
Object name
Identifier
BV16
Run/Stop
BV17
General Enabling
BV18
Direction of Rotation
BV19
JOG
BV20
LOC/REM
BV21
Second Ramp Use
BV22
Quick Stop
BV23
Fault reset
BV24
Reserved
BV25
Reserved
BV26
Reserved
BV27
Reserved
BV28
Reserved
BV29
Manual/Auto Internal PID
BV30
Manual/Auto external PID 1
BV31
Manual/Auto external PID 2
NOTE!
In order to have those commands executed, it is necessary that the inverter be programmed to be
controlled via serial. This programming is achieved by means of parameters P0105 and P0220 to
P0228.
5.1.7

DEVICE OBJECT

The BACnet equipment characteristics are describe in the DEVICE object. Its properties are described in the
Table 5-1. There must be only one DEVICE object in BACnet equipment. The Object Name property is
describes in the Table 5-10.
Property
Object Name
5.1.8

MBOX

It is a structure that allows reading and writing CFW701 parameters. The following objects compose this
structure:
ANV100: informs the parameter number
ANV101: informs the datum read from or written into the parameter
BV100: parameter reading command
BV101: parameter writing command
Procedure for reading a parameter via MBOX:
1. Inform the parameter number in the ANV100 object Present Value property;
2. Write 1 in the BV100 object Present Value property;
3. Check the value read in the ANV101 object Present Value property. The read value will be an integer,
without the decimal point representation. E.g., 20.0 will be read as 200 in the MBOX.
Procedure for writing a parameter via MBOX:
Table 5-9: Parameter P0682 BINARY VALUE objects
Run/stop
(P0682 parameter BIT 0)
General enable
(P0682 parameter BIT 1)
Speed direction
(P0682 parameter BIT 2)
JOG
(P0682 parameter BIT 3)
LOC/REM
(P0682 parameter BIT 4)
Second ramp
(P0682 parameter BIT 5)
Quick Stop
(P0682 parameter BIT 6)
Fault reset
(P0682 parameter BIT 7)
Manual/Auto Internal PID
(P0682 parameter BIT 13)
Manual/Auto external PID 1
(P0682 parameter BIT 14)
Manual/Auto external PID 2
(P0682 parameter BIT 15)
Table 5-10: Object Name property
Size
48 characters
ANSI X3.4 (US-ASCII)
BACnet Object Modeling
Description
Type
Value Default
Access
Active/inactive
type
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
CFW701
CFW701 | 28