Cfw701 Bacnet Objects; Analog Input (Ani) Object; Analog Output (Ano) Object; Analog Value (Anv) Object - WEG bacnet CFW701 User Manual

Hide thumbs Also See for bacnet CFW701:
Table of Contents

Advertisement

The Object Type values are defined by the BACnet specification, and object instance is defined by the
manufacturer for each object available for communication.
Each object can present one of the following access types:
R
Read-only
C
Commandable object. Presents a priority arrangement
W
Write-only
W/R
Writing and reading
The commandable (C) access type presents a 16-level priority arrangement, where priority 1 is the highest and
16 the lowest. If all the priorities are disabled (NULL), the value of the Relinquish Default property is given to the
Present Value property.
5.1

CFW701 BACNET OBJECTS

The parameters of frequency inverter CFW701 are mapped through BACnet objects which are described below.
NOTE!
Check the product manual for parameters details.
5.1.1

ANALOG INPUT (ANI) OBJECT

It represents an analog input that can have its value read by the controller. CFW701 ANALOG INPUT type
objects are described in the Table 5-2. The ANALOG INPUT objects are of the REAL type.
Object
Object name
Identifier
ANI0
AI1 Value
ANI1
AI2 Value
ANI2
AI3 Value
5.1.2

ANALOG OUTPUT (ANO) OBJECT

It represents an analog output that can have its value written by the controller. CFW701 ANALOG OUTPUT type
objects are described in the Table 5-3. The ANALOG OUTPUT objects are of the REAL type.
Object
Object name
Identifier
ANO0
AO1 Value
ANO1
AO2 Value
5.1.3

ANALOG VALUE (ANV) OBJECT

They represent system control parameters that can be read, written or commanded by the controller. CFW701
ANALOG VALUE type objects are described in the Table 5-4. The ANALOG VALUE objects are of the REAL
type.
Object
Object name
Identifier
ANV0
Motor Speed
ANV1
Motor Current
ANV2
DC Link Voltage (Ud)
ANV3
Motor Frequency
ANV4
Motor Voltage
ANV5
Motor Torque
ANV6
Output Power
ANV7
IGBTs Temperature U
Object Type – 10 bits
Table 5-2: ANALOG INPUT objects
Description
Accesses the contents of the parameter P0018
Accesses the contents of the parameter P0019
Accesses the contents of the parameter P0020
Table 5-3: ANALOG OUTPUT objects
Accesses the contents of the parameter P0696
Accesses the contents of the parameter P0697
Table 5-4: ANALOG VALUE objects
Motor speed – P0002
Motor current – P0003
DC link voltage – P0004
Motor frequency – P0005
Motor voltage – P0007
Motor torque – P0009
Output power – P0010
Temperature of the U IGBTs – P0030
Object instance– 22 bits
Description
Description
BACnet Object Modeling
Unit
Access type
%
%
%
Unit
Access type
-
C
-
C
Access
Unit
RPM
Amps
V
Hz
V
%
KW
°C
CFW701 | 25
R
R
R
type
R
R
R
R
R
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading