BACnet instance = BACnet ID + Serial address
Example 1: serial address = 102
Instance = 359102
Example 2: serial address = 15
Instance = 359015
NOTE!
The instance created automatically is not showed at the parameters P0760 and P0761, which remain
with the value 0.
Manual:
The BACnet instance is defined by using the parameters P0760 and P0761. The P0760 parameter content is
multiplied by 10000 and added to the P0761 parameter content.
Example 1: Instance = 542786
542786 / 10000 = 54.2786
P0760 = 54 (whole part)
P0761 = 2786 (fractional part)
Example 2: Instance = 66789
66789 / 10000 = 6.6789
P0760 = 6 (whole part)
P0761 = 6789 (fractional part)
Example 3: Instance = 35478
35478 / 10000 = 3.5478
P0760 = 3 (whole part)
P0761 = 5478 (fractional part)
NOTE!
The parameters P0760 and P0761 allow adjusting a maximum value of 4199999. However, the
maximum instance value will be 4194304.
NOTE!
The equipment must be initialized when the contents of parameters P0760 and P0761 are changed.
P0762 – MAXIMUM MASTER NUMBER
Range:
0 to 127
Properties:
CFG
Access groups via HMI:
Description:
It allows programming the longest address used by a master in the BACnet network, optimizing the
communication. All the network devices must be set with the same value in this parameter.
With the standard value (127) for this parameter, any address set for the device can participate in the
communication. However, that will make the devices in the network send requests searching for devices in all
NET
Inverter Programming
Default: 127