Ethernet Configuration - ABB REL670 Operator's Manual

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Section 9
Read and change settings
9.2.2.5
44
Includes available instances of GOOSE binary receive (GB) where setting Operation
can be set On or Off.
IEC61850–8–1
Main menu/Settings/General settings/Communication/Station communication/
IEC61850–8–1
Includes settings for the IED name, operation (on/off) and GOOSE.
Multicommand send
Main menu/Settings/General settings/Communication/Station communication/
MultiCommandSend/MT
Includes available instances of Multicommand send settings allowing the user to adjust
the maximum and minimum cycle time.
Multicommand receive
Main menu/Settings/General settings/Communication/Station communication/
MultiCommandReceive/CM
Includes available instances of Multicommand receive settings allowing the user to
adjust the maximum and minimum cycle time, the pulse duration and mode of
operation. The mode of operation is either steady or pulsed.
Horizontal communication via GOOSE for interlocking
Main menu/Settings/General settings/Communication/Station communication/
ReceivingInterlInfo/GR
Includes available instances of (GR01–GR59) for horizontal communication via
GOOSE. Each instance or set can be switched On or Off via the Operation On and Off
parameter.

Ethernet configuration

Main menu/Settings/General settings/Communication/Ethernet configuration/
Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are set
here. These are generally used when connecting a PC directly to the IED. Remember
that this is a static IP address and that the appropriate network settings must also be
made in the PC.
1MRK506276-UUS B
Operator's manual