Displays available instances of SESRSYN (25) with a number of measurements per
instance. These include information about which lines and buses selected, various
voltage and frequency differences and feedback on synchronization status.

Monitoring

Monitoring includes large amounts of viewable data including Disturbance report data,
Service values, Current phasors, Voltage phasors, Milliampere signal level supervision,
Fault locator, Binary signal status report, Events, MVGGIO, MVExpander and LEDs.

Logical signal status report BINSTATREP

Main menu/Test/Function status/Monitoring/BinarySignalStatusReport/SSR
Displays sets of output measurements with several outputs per set of measurements.

Disturbance report DRPRDRE

Test/Function status/Monitoring/DisturbanceReport(RDRE)
Displays data about disturbance reports. The disturbance report can be switched off, a
disturbance report that has been initiated is indicated by a boolean number, as are
completed reports and cleared reports. The parameter MEM USED indicates that more
than 80% of the memory space available for disturbance report data has been used and
the need to clear the memory is pressing. The Memory USED parameter generates an
integer value showing the actual amount of memory used by the disturbance record
repository. The maximum number of incoming analog channels is 40 and their Trig
status is indicated here. The Fault number parameter generates an integer indicating
the number of faults recorded since the last clearing of the memory.

Event counter CNTGGIO

Main menu/Test/Function status/Monitoring/EventCounter(GGIO)/CNT
Display the output data of the CNTGGIO function.

Fault locator LMBRFLO

Main menu/Test/Function status/Monitoring/FaultLocator(RFLO)/FLO
Displays instances with some measurements.

Generic measured value MVGGIO

Section 11
Test the IED
89