Analog And I/O Modules; Overview; Analog Modules - ABB REL670 Operator's Manual

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

1MRK506276-UUS B
9.2.3
9.2.3.1
9.2.3.2
Operator's manual
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port AB
The IP address, IP mask and Mode for the IEC 61850-8-1 communication using the
Optical Ethernet Module (OEM) at the rear of the IED are set here.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port CD
The IP address (with different IP address when a second channel is used), IP mask and
Mode for the Optical Ethernet Module (OEM) at the rear of the IED are set here. The
CD port is used for IEC 61850-9-2LE communication.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM - Redundant PRP
Redundant station bus communication IEC61850-8-1 are set here.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Gateway
If a gateway is used to access the system the address to that gateway is entered here.

Analog and I/O modules

Overview

Under Analog modules in the General settings menu there are settings for Analog
inputs and I/O modules. Within each instance of analog input there are settings for all
12 channels that include the name of the channel, star point of the CT circuit, the
primary and secondary values from the measuring transformers (CTs and VTs). The
channel type and ratings are shown but cannot be changed.
The settings for binary inputs and outputs even include the milliampere input modules.
A mix of up to 14 instances of BIM, BOM and IOM is possible depending on the
physical configuration of the IED. Operation ON or OFF can be set for all of these and
for the BIMs oscillation release and oscillation block settings are available. These
settings are on board level and apply to all binary inputs or outputs on a board.

Analog modules

Main menu/Settings/General Settings/Analog modules/AnalogInputs
Displays all variations of analog input modules with parameters. The analog input
modules have different combinations of current and voltage inputs. Each channel has
Section 9
Read and change settings
45

Advertisement

Table of Contents
loading

Table of Contents