Start Up and Commissioning
NOTICE
Chapter 4.2 Applying Power and chapter 4.3 Basic
Operational Programming conclude the procedures for
applying power to the frequency converter, basic
programming, set-up, and functional testing.

4.5 System Start Up

Complete user wiring and application programming before
performing the procedure in this section. See
chapter 7 Application Examples for application set-up
information. The following procedure is recommended
after application set-up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
1.
Press [Auto On].
2.
Ensure that external control functions are
properly wired to the frequency converter and all
programming is completed.
3.
Apply an external run command.
4.
Adjust the speed reference throughout the speed
range.
5.
Remove the external run command.
6.
Note any problem.
If warnings or alarms occur, see chapter 9 Warnings and
Alarms.
MG16D302
Operating Instructions
Danfoss A/S © Rev. 06/2014 All rights reserved.
4
4
39

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FC 102 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vlt aqua drive fc 202

Table of Contents

Save PDF