Application Examples
7.3 Connection Examples for Control of
Motor with External Signal Provider
NOTICE
The following examples refer only to the frequency
converter control card (right LCP), not the filter.
7.3.1 Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [8] Start
Terminal 27 = 5-12 Terminal 27 Digital Input [0] No
operation (Default coast inverse)
Terminal 37 = Safe stop
7
7
Speed
Start/Stop
[18]
Illustration 7.5 Start/Stop Parameters
7.3.2 Pulse Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [9] Latched
start
Terminal 27= 5-12 Terminal 27 Digital Input [6] Stop inverse
Terminal 37 = Safe torque off
58
Operating Instructions
12 13 18
19
27
29
32
33 20
37
Start/Stop
Safe Stop
Danfoss A/S © Rev. 06/2014 All rights reserved.
12
13
18
19
27
29
32
Start
Stop inverse
Speed
Start (18)
Start (27)
Illustration 7.6 Pulse Start/Stop Parameters
7.3.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = 5-10 Terminal 18 Digital Input [9]
Start (default)
Terminal 27 = 5-12 Terminal 27 Digital Input [19]
Freeze reference
Terminal 29 = 5-13 Terminal 29 Digital Input [21]
Speed up
Terminal 32 = 5-14 Terminal 32 Digital Input [22]
Speed down
Illustration 7.7 Speed Control Parameters
33
20
37
Safe Stop
12
+24V
18
Par. 5-10
27
Par. 5-12
29
Par. 5-13
32
Par. 5-14
37
MG16D302