Danfoss FC 102 Operating Instructions Manual page 59

Vlt series hvac drive
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 7.13 Using SLC to Set a Relay
MG16D302
Operating Instructions
Parameters
Function
Setting
4-30 Motor
[1] Warning
Feedback Loss
Function
4-31 Motor
100 RPM
Feedback Speed
Error
4-32 Motor
5 s
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start
[19] Warning
Event
13-02 Stop
[44] Reset
Event
key
13-10 Comparat
[21] Warning
or Operand
no.
13-11 Comparat
[1] ≈*
or Operator
13-12 Comparat
90
or Value
13-51 SL
[22]
Controller Event
Comparator 0
13-52 SL
[32] Set
Controller Action
digital out A
low
5-40 Function
[80] SL digital
Relay
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 is issued. The SLC monitors
Warning 90 and in the case
that Warning 90 becomes TRUE
then relay 1 is triggered.
External equipment may
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the frequency converter
continues and the warning
disappears. But relay 1 is still
triggered until [Reset] on the
LCP.
Danfoss A/S © Rev. 06/2014 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 7.14 Mechanical Brake Control (Open Loop)
1-76
Current
Speed
1-71
Start (18)
Start
reversing (19)
Relay output
Open
Closed
Illustration 7.4 Mechanical Brake Control (Open Loop)
Parameters
Function
Setting
1-00 Configu-
[0] Speed
ration Mode
open loop
1-01 Motor
+
[1] VVC
Control Principle
5-40 Function
[32] Mech.
Relay
brake ctrl.
5-10 Terminal 18
[8] Start*
Digital Input
5-11 Terminal 19
[11] Start
Digital Input
reversing
1-71 Start Delay
0.2
1-72 Start
+
[5] VVC
/
Function
FLUX
Clockwise
1-76 Start
I
m,n
Current
2-20 Release
App.
Brake Current
dependent
2-21 Activate
Half of
Brake Speed
nominal slip
[RPM]
of the motor
*=Default Value
Notes/comments:
Time
2-21
1-71
2-21
57
7
7