Fault codes
(cont.)
Fault
Const.
Weath.-
code on
comp.
the dis-
play
C6
X
C7
X
X
Cd
X
X
CE
X
X
CF
X
dA
X
db
X
System char-
Cause
acteristics
Control mode,
Communica-
max. pump
tion fault,
speed
external vari-
able speed
heating circuit
pump, heat-
ing circuit with
mixer M2
Control mode,
Communica-
max. pump
tion fault,
speed
external vari-
able speed
heating circuit
pump, heat-
ing circuit A1
Control mode
Communica-
tion fault,
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault, ext.
extension
Control mode
Communica-
tion fault,
LON commu-
nication mod-
ule
Control mode
Short circuit,
without room
room temper-
influence
ature sensor,
heating circuit
A1
Control mode
Short circuit,
without room
room temper-
influence
ature sensor,
heating circuit
with mixer
M2
Troubleshooting
Measures
Check setting of
coding address
"E5".
Check setting of
coding address
"E5".
Check connec-
tions, Vitocom 100
and coding
address "95".
Check connections
and coding
address "2E".
Replace the LON
communication
module.
Check the room
temperature sen-
sor, heating circuit
A1.
Check the room
temperature sen-
sor, heating circuit
with mixer M2.