Viessmann VITODENS 200-W Service Instructions Manual page 68

Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault
Const.
Weath.-
code on
comp.
the dis-
play
92
X
X
93
X
X
94
X
X
9A
X
X
9b
X
X
68
System char-
Cause
acteristics
Control mode
Short circuit,
collector tem-
perature sen-
sor; connects
to the
Vitosolic at
S1
Control mode
Short circuit,
cylinder tem-
perature sen-
sor; connects
to the
Vitosolic at
S3
Control mode
Short circuit,
temperature
sensor; con-
nects to the
Vitosolic at
S2
Control mode
Lead break,
collector tem-
perature sen-
sor; connects
to the
Vitosolic at
S1
Control mode
Lead break,
cylinder tem-
perature sen-
sor; connects
to the
Vitosolic at
S3
Measures
Check the sensor
at the Vitosolic.
Check the sensor
at the Vitosolic.
Check the sensor
at the Vitosolic.
Check the sensor
at the Vitosolic.
Check the sensor
at the Vitosolic.

Advertisement

Table of Contents
loading

Table of Contents