Coding in the delivered condition
User no.
77:1
LON user number
Summer econ. A1/M2
A5:5
With heating circuit pump
logic function (only for
weather-compensated
control units)
Min. flow temp. A1/M2
C5:20
Electronic minimum flow
temperature limit 20 °C
(only for weather-com-
pensated control units)
Max. flow temp. A1/M2
C6:75
Electronic maximum flow
temperature limit 75 °C
(only for weather-com-
pensated control units)
Slope A1/M2
d3:14
Heating curve slope = 1.4
(only for weather-com-
pensated control units)
Level A1/M2
d4:0
Heating curve level = 0
(only for weather-com-
pensated control units)
Possible change
77:2
LON subscriber number,
to
adjustable from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number only
once.
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
the boiler coding card)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C
C6:127
d3:2
Heating curve slope adjust-
to
able from 0.2 to 3.5 (see
d3:35
page 29)
d4:–13
Heating curve level adjust-
to
able from –13 to 40 (see
d4:40
page 29)