Codes
Code 2
(cont.)
Coding in the delivered condition
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW tempera-
ture
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
65:...
Information regarding the
type of diverter valve (not
adjustable)
67:40
With Vitosolic: Third set
DHW temperature =
40 °C
6F:...
Maximum output for
DHW heating in %;
defaulted by the boiler
coding card
71:0
DHW circulation pump
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:0
DHW circulation pump
"ON" in accordance with
the time program (only for
weather-compensated
control units)
44
Possible change
60:5
The difference between the
to
boiler water temperature
60:25
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
65:0
Without diverter valve
65:1
Viessmann diverter valve
65:2
Wilo diverter valve
65:3
Grundfos diverter valve
67:0
Without third set DHW tem-
perature
67:1
Third set DHW tempera-
to
ture adjustable from 1 to
67:60
60 °C (depending on set-
ting of coding address
"56")
6F:0
Max. output during DHW
to
heating adjustable from 0
6F:100
to 100 %
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value