Code 2
(cont.)
Coding in the delivered condition
E1:1
With remote control: The
set day temperature can
be adjusted at the remote
control unit from 10 to
30 °C (only for weather-
compensated control
units)
E2:50
With remote control: No
display correction for the
actual room temperature
(only for weather-com-
pensated control units)
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 hours (only for weather-
compensated control
*1
units)
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode 12 min
(only for constant temper-
ature control units)
*1
In the "Heating and DHW" program, party mode ends automatically when the
system changes over to operation with standard room temperature.
Possible change
E1:0
Set day temperature
adjustable from 3 to 23 °C
E1:2
Set day temperature
adjustable from 17 to
37 °C
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
F1:1
Screed drying function
to
adjustable in accordance
F1:6
with 6 optional tempera-
ture/time profiles (see
page 97)
F1:15
Constant flow temperature
20 °C
F2:0
No time limit for party mode
F2:1
Time limit adjustable from 1
to
to 12 hours
F2:12
F5:0
No run-on time for the inter-
nal circulation pump
F5:1
Run-on time of the internal
to
circulation pump adjusta-
F5:20
ble from 1 to 20 min
Codes