Chapter 8 Appendix
 When MODE2 is selected
 When MODE3 is selected
8.4 Offset Function
8-20
With OFFSET value set at -1°C, TEMP PV and communication data express
"29°C" (circulating fluid discharge temp. value + OFFSET value) that agrees with
the temperature of the circulating fluid in your system.
This system
Communication data
TEMP PV 29 ℃
TEMP PV 29 ℃
External communication
TEMP SP 30 ℃
Discharge temp.:
OFFSET -1 ℃
30 ℃
Circulating fluid temp. in
your system: 29 ℃
Figure 8-8 When MODE2 is selected
This mode enables this system to exercise temperature control to obtain 31°C
(TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the
discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal
dissipation is assured to allow the circulating fluid in your system to be 30°C.
TEMP SP value is obtained for your system. TEMP PV and communication data
also express "30°C" (circulating fluid discharge temp. value - OFFSET value) that
agrees with the temperature of the circulating fluid in your system.
This system
Communication data
TEMP PV 30 ℃
TEMP PV 30 ℃
External communication
TEMP SP 30 ℃
Discharge temp:
OFFSET
31 ℃
1
Circulating fluid temp. in
your system: 30 ℃
Figure 8-9 When MODE3 is selected
Your system
TEMP PV
29 ℃
Heat dissipation:
1 ℃
Your system
TEMP PV
30 ℃
dissipation:
Heat
1 ℃
HRZ Series