 Specification for fluorinated fluid (wide temperature)
Table 8-3 Specification for Fluorinated Fluid (Wide Temperature)
Model
Cooling method
*1
Cooling capacity
(50Hz/60Hz)
Operating temperature range
Temperature stability
Circulating fluid
Refrigerant
*4
Pump capacity
(50Hz/60Hz)
*5
Main Tank capacity
*6
Sub Tank capacity
Circulating fluid port
Facility water
Required flow of facility water
(50Hz/60Hz)
Facility water port
Power supply
Main breaker size
*7
Dimensions
*8
Weight
Communication
*1: The capacity is derived under the conditions that the facility water temp. is 25°C and that the circulating fluid flow
rate is obtained at a specified flow rate of pump capacity. Applied to 50 / 60Hz.
*2: This is a system output temperature, with flow rate defined in pump capacity secured, when stabilized with no
disturbance. Its upper limit may be violated if an insufficient amount of the circulating fluid is present or a
disturbance to flow rate is observed.
®
*3: Galden
is a registered trademark of Solvay Solexis, and Fluorinert
*4: The capacity is derived at the Outlet of this system when the circulating fluid temp. is at 20°C.
*5: This is a minimum amount of the fluid for operation of the Thermo Chiller outfitted with internal piping and heat
exchanger in this system. Circulating fluid temp.: 20°C
*6: This is an auxiliary space with a main tank capacity excluded. Available for circulating fluid recovery from external
piping and backup supply.
*7: This is the dimensions of panels, which is derived without protrusions such as a breaker handle.
*8: This is the mass of the system when it contains no circulating fluid.
*9: Facility water temp. is 25°C. There is required flow when adding load described on cooling capacity.
HRZ Series
HRZ002-W
kW
2.0 (At 20°C)
°C
°C
Galden
Galden
MPa
L
L
°C/MPa
*9
L/min
(1.6/1.8[gal/min])
A
mm
W380D870H950(W14.96xD34.25xH37.40[inch])
kg
Serial RS-485 (Dsub-9pin) , Contact signal (Dsub-25pin)
Water cooled refrigerant
-20 to 90
*2
±0.1
®
*3
TM
HT135
Fluorinert
FC-3283
®
*3
TM
HT200
Fluorinert
FC-40
(No intrusion of foreign body)
R404A(HFC) (CFC Free),
(GWP:3922)
0.45 /0.65 (At 20L/min)
(65 / 94 [PSIG] At 5.3[gal/min])
Approx.15 (4 [gal])
Approx.16 (4.2 [gal])
Rc 3/4
10 to 25 / 0.3 to 0.7 (45 to 100 [PSIG])
6/7
Rc 1/2
3-phase 50/60Hz AC200/200 to 208V±10%
30
165 (364 [lbs])
TM
is a trademark of U.S. 3M.
HRX-OM-I051
Chapter 8 Appendix
HRZ008-W
8.0 (At 20°C)
*3
(-20 to 40°C)
*3
(20 to 90°C)
13/14
(3.4/3.7[gal/min])
8.1 Specification
8-3