Chapter 5 System Operation
This screen enables the setting of set values.
No.
Item
1
TEMP BAND
1.0 to 5.0°C
TEMP
2
10 to 480sec
READY
3
OFFSET
-20.0 to 20.0°C
OFF, MODE1, MODE2,
4
OFFSET
MODE3
HRZ□□□-L□: -20 to 45°C
HRZ□□□-L2 : 10 to 45°C
5
HIGH TEMP
HRZ□□□-H□: 20 to 93°C
HRZ□□□-W□: -20 to 93°C
0, 15 to 40 LPM
0, 4 to 10.6 GPM
6
LOW FLOW
0, 8 to 40 LPM
0, 2.1 to 10.6 GPM
(Only for HRZ010-W*S)
7
FLOW UNIT
LPM, GPM
8
PRESS UNIT
MPa, PSI
SLAVE
9
1 to 16CH
ADRS.
N/A
10
OUT
ALARM1 to 25
TEMP READY,
11
E_OUT
AUTO PURGE
5.3 Operation Screen
5-8
Table 5-10 Initial Setting Screen
Setting range
*1
Allows the selection of the band width for TEMP SP.
Allows the setting of the time from TEMP PV value
*1
reaching BAND range to TEMP READY is displayed
and put out.
Calibrates variations in temperature between this
*2
system and your system.
(See "Appendix 8.4 Offset Function" in Chapter 8 for
details.)
Issues an alarm of "Reservoir High Temp WRN" if the
circulating fluid exceeds the set temperature.
Issues an alarm of "Return Low Flow WRN" if the
circulating fluid does not reach the set flow rate.
Lift this alarm if the selection is "0".
Even if the values from 1 to 14LPM (0.3 to 3.7GPM)
are input, the setting value make 15LPM (4.0GPM).
Even if the values from 1 to 7LPM (0.3 to 1.8GPM) are
input, the setting value make 8LPM (2.1GPM).
Allows the selection of the unit of flow rate.
Allows the selection of the unit of pressure.
Allows the selection of the slave address for serial
RS-485 communication.
Allows the selection of alarm signals for contact signal.
(See Appendix 8.1.3 Alarm signal selection" for
details.)
Allows the selection of EVENTOutput.
(See Appendix 8.1.2 Communication specification" for
*1
details.)
[Tips]
Valid during option setting with "5.3.11 Option screen" on page 5-9.
See "Appendix 8.5 BAND/READ" in Chapter 8 on page 8-21 on
BAND/READY function (*1).
TEMP SP+OFFSET value (*2) should be in the TEMP SP setting range
defined in "Table 5-8 Setting Screen" on page 5-6.