Table 12: Interpreting The Static Switch Transfer Code (Loadbp) - Gamatronic power+ sa User Manual

20 kva, 30 kva, and 40 kva models
Hide thumbs Also See for power+ sa:
Table of Contents

Advertisement

Data – dc voltage between + and – terminals for all events except LOADBP and STSW
status for LOADBP events. (See below.)
Even start (IN) and end (OUT)
Description – (See Table 11 above)
Event number – 0 through 255, 255 being the most recent
Example:
This message means that at 11:23:56 on January 28
was registered as event 254; dc voltage at the time was 865 V being a sum of (V+ -N) and
(V- -N).

Table 12: Interpreting the Static Switch transfer code (LOADBP)

The STSW transfer code, given as a decimal, is the sum of the eight components listed in this table.
Each component has its own weight if detected, and a weight of zero if not detected.
C
OMPONENT
C
ONDITION DESCRIPTION
WEIGHT
Inverter voltage blackout for >3 ms.
1
2
Inverter peak voltage low (brownout) (<185 V for 3x400 V, <92.5 V for 3x208 V).
4
Inverter peak voltage high (>400 V for 3x400 V, >200 V for 3x208 V).
Frequency beyond limits (45-65 Hz).
8
16
Inverter average voltage low (<185 V for 3x400 V, <92.5 V for 3x208 V).
32
Inverter average voltage high (>260 V for 3x400 V, >130 V for 3x208 V)..
Load transfer command received from the controller (not manual).
64
128
Load transfer command received from the Static Switch (manual key press).
Example: If LOADBP data = 67 = (64+2+1), this means that three conditions were present:
(64) Instruction to transfer the load was issued by the controller.
(2) Low peak voltage detected.
(1) Voltage blackout encountered.
POWER + SA: 20, 30 and 40 kVA, Release 2.1
G
AMATRONIC
11:23:56 10.01.28 865 IN -> E.P.O. 254
E
I
L
LECTRONIC
NDUSTRIES
TD
th
2010, Emergency Power Off alarm
.
69