9.12.5
Setting Power Factor Correction
1.
Select Powr.Calib:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Enable or disable power factor correction by using the ▲▼arrow keys and Ent::
2.
[Main Menu > SETUP > (password) > Ent > Service > Configure > Powr.Calib]
-- Set power correction factor value
Current Value:
Value to modify:
------ Use Up/down, Enter Or Esc ------
Figure 242: Enabling/disabling power factor correction
9.12.6
Setting the SC2012
1.
Select SC2012:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
2.
Select Restart controller:
[Main Menu > SETUP > (password) > Ent > Service > SC2012]
1> Restart controller 3> Network...
2> Factory settings
Your selection: 1
Enter if you are sure (else press Esc.!)
A confirmation screen appears briefly and the controller restarts.
POWER + SA: 20, 30 and 40 kVA, Release 2.1
G
E
AMATRONIC
LECTRONIC
4> DryOut Test 7> --------
5> Configure
Figure 241: Service menu
01%
02%
4> DryOut Test 7> --------
5> Configure
Figure 243: Service menu
4> Reset MBX
5> --------------
Figure 244: SC2012 menu
I
L
.
NDUSTRIES
TD
8> Powr.Calib
--
8> Powr.Calib
115