4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Sub Module Serial Number
Network Address NSAP
IEC61850 Config GOOSE ConfRev
When a settings file is loaded to a C30 that is in-service, the following sequence occurs:
1.
The C30 takes itself out of service.
2.
The C30 issues a
3.
The C30 closes the critical fail contact.
c) CREATING AND EDITING FLEXLOGIC
You create or edit a FlexLogic equation in order to customize the relay. You can subsequently view the automatically gener-
ated logic diagram.
d) VIEWING ACTUAL VALUES
4
You can view real-time relay data such as input/output status and measured parameters.
e) VIEWING TRIGGERED EVENTS
While the interface is in either online or offline mode, you can view and analyze data generated by triggered specified
parameters, via one of the following:
Event recorder
The event recorder captures contextual data associated with the last 1024 events, listed in chronological order from
most recent to oldest.
Oscillography
The oscillography waveform traces and digital states are used to provide a visual display of power system and relay
operation data captured during specific triggered events.
f) FILE SUPPORT
Execution: Any EnerVista UR Setup file that is opened launches the application or provides focus to the already
opened application. If the file was a settings file (has a URS extension) that had been removed from the Settings List
tree menu, it is added back to the Settings List tree menu.
Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files that are dropped into the Settings List window are added to the tree, which is automatically sorted alphabeti-
cally with respect to settings file names. Files or individual menu items that are dropped in the selected device menu in
the Site List window are automatically sent to the online communicating device.
g) FIRMWARE UPGRADES
The firmware of a C30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic "Upgrading Firmware".
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of firm-
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
NOTE
The
EEPROM DATA ERROR
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
4-2
major self-test error.
UNIT NOT PROGRAMMED
message displayed after upgrading/downgrading the firmware is a resettable, self-test
C30 Controller System
4 HUMAN INTERFACES
GE Multilin