GE C30 Instruction Manual page 198

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5.4 SYSTEM SETUP
SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate a contact output to
open disconnect switch 1.
SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate a contact output to
close disconnect switch 1.
SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWTCH 1 A/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 89/a status input to create a logic 1 when
the disconnect switch is closed. If the
as the operand used to track the disconnect switch open or closed position. If the mode is selected as "1-Pole", the
input mentioned above is used to track phase A and the
track phases B and C, respectively.
SWTCH 1 A/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed 89/
b status input to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available,
then an inverted 89/a status signal can be used.
SWITCH 1 B CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
SWITCH 1 B OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
SWITCH 1 C CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
5
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
SWITCH 1 C OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the C30 is in "Programmed" mode and not in the local control mode.
NOTE
5-82
setting is selected as "3-Pole", this setting selects a single input
SWITCH 1 MODE
SWITCH 1
FlexLogic operand is asserted from alarm or blocking purposes.
C30 Controller System
and
settings select operands to
B
SWITCH 1
C
5 SETTINGS
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents