5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
 TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GENERAL
 GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
5
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP

TRANSMISSION
GSEE
 GSSE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In C30 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
5-28

COMMUNICATIONS
 GENERAL
 GSSE
MESSAGE
 FIXED GOOSE
MESSAGE
 CONFIGURABLE
MESSAGE
 GOOSE

COMMUNICATIONS
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed C30 GOOSE, and configurable GOOSE.

COMMUNICATIONS
GSSE FUNCTION:
Enabled
GSSE ID:
MESSAGE
GSSEOut
DESTINATION MAC:
MESSAGE
000000000000
setting.
C30 Controller System

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: 1 to 60 s in steps of 1

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address